Datasheet
CP1E-E@@(S)D@-@ CP1E-N@@(S@)D@-@/NA20D@-@
33
●Transistor Outputs (Sinking or Sourcing)
*1 If the ambient temperature is maintained below 50°C, up to 0.9 A/common can be used.
*2 The fuse cannot be replaced by the user. Replace the Unit if the fuse breaks due to an short-circuit or overcurrent.
*3 Do not connect a load to an output terminal or apply a voltage in excess of the maximum switching capacity.
Item
Specification
CP1W-40EDT
CP1W-40EDT1
CP1W-32ET
CP1W-32ET1
CP1W-20EDT
CP1W-20EDT1
CP1W-16ET
CP1W-16ET1
CP1W-8ET
CP1W-8ET1
Max. switching capacity
*1
4.5 to 30 VDC
0.3 A/output
4.5 to 30 VDC
0.3 A/output
24 VDC +10%/-5%
0.3 A/output
4.5 to 30 VDC
0.3 A/output
4.5 to 30 VDC
0.3 A/output
0.9 A/common
3.6 A/Unit
0.9 A/common
7.2 A/Unit
0.9 A/common
1.8 A/Unit
0.9 A/common
3.6 A/Unit
0.9 A/common
1.8 A/Unit
Leakage current 0.1 mA max. 0.1 mA max. 0.1 mA max. 0.1 mA max. 0.1 mA max.
Residual voltage 1.5 V max. 1.5 V max. 1.5 V max. 1.5 V max. 1.5 V max.
ON delay 0.1 ms max. 0.1 ms max. 0.1 ms. 0.1 ms max. 0.1 ms max.
OFF delay
1 ms max.
24 VDC +10%/-5%
5 to 300 mA
1 ms max.
24 VDC +10%/-5%
5 to 300 mA
1 ms max.
24 VDC +10%/-5%
5 to 300 mA
1 ms max.
24 VDC +10%/-5%
5 to 300 mA
1 ms max.
24 VDC +10%/-5%
5 to 300 mA
Max. number of
Simultaneously ON
Points of Output
16 pts (100%) 24 pts (75%) 8 pts (100%) 16 pts (100%) 8 pts (100%)
Fuse *2 1 fuse/common
Circuit configuration
COM (−)
OUT
OUT
L
L
COM (+)
OUT
OUT
L
L
Sinking Outputs Sourcing Outputs
Output LED
Output LED
Internal
circuits
Internal
circuits
24 VDC/4.5
to 30 VDC
24 VDC/4.5
to 30 VDC
0.9
0.8
(A)
0
(°C)
50 55
Ambient tem
p
erature
Total current for common