Datasheet
CP1E-E@@(S)D@-@ CP1E-N@@(S@)D@-@/NA20D@-@
37
Serial Communications Port for N/NA@@(S@)-type CPU Units
The Serial Communication Port can be used for a CP1E N/NA@@(S@)-type CPU Unit.
N30/40/60 or NA20 CPU Units
One built-in RS-232C port and one Option Board can be used.
Note: Option Boards cannot be used for CP1E N14/20 CPU Units.
N30/40/60S1 CPU Units N30/40/60S CPU Units
Built-in RS-232C, RS-485 ports. Built-in RS-232C port.
N14/20 CPU Units
Built-in RS-232C ports.
Built-in
RS-232C
Built-in RS-2485
Built-in
RS-232C
CP1W-CIF11/12
RS-422A/485 Option
Board
CP1W-CIF01
RS-232C Option
Board
Built-in
RS-232C port
CP1W-CIF41
Ethernet Option
Board version 2.0 or higher
IP ADDRESS:
SUBNET MASK:
COMMERR
10BASE-T
100BASE-TX
Optional Serial Communication Board
Note: The Optional Serial Communication Board cannot be used for CP1E
N/NA@@S(1)-type CPU Units and E@@-type CPU Units.
Model number Port
Maximum
transmission
distance
Connection method
CP1W-CIF01 One RS-232C port 15 m
Connector
(D-sub, 9 pin female)
CP1W-CIF11
One RS-422A/485 port
(not isolated)
50 m
Terminal block
(using ferrules)
CP1W-CIF12
One RS-422A/485 port
(isolated)
500 m
Terminal block
(using ferrules)
CP1W-CIF41 One Ethernet port 100 m
Connector
(RJ45, 8 pin modular)
Built-in
RS-232C port