Datasheet

CP1L
20
■ Ethernet Communications Specifications (CP1W-CIF41)
Note: 1. CX-Programmer version 8.1 or higher (CX-One version 3.1 or higher) is required.
2. Use CX-Integrator version 2.33 or higher (CX-One version 3.1 or higher) when the system needs to be set the routing tables. However, CX-Integrator does
not support the other functions, using CP1W-CIF41, such as transferring the parameters and network structure.
3. To connect the CP1H/CP1L CPUs with the NS-series Programmable Terminals via Ethernet using CP1W-CIF41, make sure that the system version of NS
Series is 8.2 or higher.
■ Analog I/O Option Board (CP1W-ADB21/DAB21V/MAB221)
Note: CP1L-EL CPU Unit or CP1L-EM CPU Unit only.
Item Specifications
Applicable PLCs
CP1L CPU Units
Note: The Ethernet Option Board cannot be used for the CP1L-EM/EL/L10.
Number of Units that can be mounted
2 sets. (The CP1W-CIF41 Ver.1.0 and Ver.2.0 can be combined and used with one CPU Unit. When using
CP1W-CIF41 Ver.1.0, only one unit can be mounted in an option board slot.)
Protocol used TCP/IP, UDP
Server/Client Only server (Cannot be used as a client)
Applications FINS
Transfer
Media access method CSMA/CD
Modulation method Baseband
Transmission paths Star form
Baud rate 100 Mbit/s (100Base-TX), 10 Mbit/s (10Base-T)
Transmission media
100 Mbit/s
• Unshielded twisted-pair (UDP) cable
Categories: 5, 5e
• Shielded twisted-pair (STP) cable
Categories: 100 Ω at 5, 5e
10 Mbit/s
• Unshielded twisted-pair (UDP) cable
Categories: 3, 4, 5, 5e
• Shielded twisted-pair (STP) cable
Categories: 100 Ω at 3, 4, 5, 5e
Transmission Distance 100 m (distance between hub and node)
Item FINS Communications Service Specifications
Number of nodes 254
Message length 1016 bytes max.
Size of buffer 8k
Communications Function FINS Communications Service (UDP/IP, TCP/IP)
FINS/UDP
method
Protocol used UDP/IP
Port number 9600 (default) Can be changed.
Protection No
FINS/TCP
method
Protocol used TCP/IP
Number of connections Up to 2 simultaneous connections and only one connection can be set to client
Port number 9600 (default) Can be changed.
Protection Yes (Specification of client IP addresses when unit is used as a server)
Product name Model
Specifications
Input Output
Conversion time
Voltage Input
0V to 10V
Current Input
0mA to 20mA
Voltage Output
0V to 10V
Resolution:1/4000 Resolution:1/2000 Resolution:1/4000
Analog Input Option Board CP1W-ADB21 2CH - 2ms/point
Analog Output Option Board CP1W-DAB21V - 2CH 2ms/point
Analog I/O Option Board CP1W-MAB221 2CH 2CH 6ms/4point