CPU Units and Expansion Units 11
Temperature Sensor Units: CP1W-TS001/TS002/TS101/TS102
By mounting a Temperature Sensor Unit to the PLC, inputs can be obtained from thermocouples or platinum resistance thermometers, and
temperature measurements can be converted to binary data (4-digit hexadecimal) and stored in the input area of the CPU Unit.
Specifications
Note: The indication accuracy when using a K-type thermocouple for temperature less than -100C is 4C1 digit max.
Input Temperature Ranges for CP1W-TS001/002
(The rotary switch can be used to make the following range
and input type settings.)
Input Temperature Ranges for CP1W-TS101/102
(The rotary switch can be used to make the following range
and input type settings.)
CP1W-SRT21 CompoBus/S I/O Link Unit
The CompoBus/S I/O Link Unit functions as a slave for a CompoBus/S Master Unit (or an SRM1 CompoBus/S Master Control Unit) to form an I/
O Link with 8 inputs and 8 outputs between the CompoBus/S I/O Link Unit and the Master Unit.
Item Model CP1W-TS001/002 CP1W-TS101/102
Number of inputs 2 (TS001), 4 (TS002) 2 (TS101), 4 (TS102)
Input types K, J switchable (Note: Same for all inputs.) Pt100, JPt100 switchable (Note: Same for all inputs.)
Indication accuracy (The larger of the indicated value: 0.5% and 2C (See note.))
1 digit max.
(The larger of the indicated value: 0.5% and 1C) 1 digit max.
Conversion time 250 ms/2 points (TS001, TS101); 250 ms/4 points (TS002, TS102)
Converted
temperature data
Binary (4-digit hexadecimal)
Isolation method Photocoupler isolation between the temperature input signals.
Input type Range (C) Range (F)
K -200 to 1300 -300 to 2300
0.0 to 500.0 0.0 to 900.0
J -100 to 850 -100 to 1500
0.0 to 400.0 0.0 to 750.0
Input type Range (C) Range (F)
Pt100 -200.0 to 650.0 -300 to 1200.0
JPt100 -200.0 to 650.0 -300 to 1200.0
Specifications
Item Model CP1W-SRT21
Master/Slave CompoBus/S Slave
Number of I/O bits 8 input bits, 8 output bits
Number of words
occupied in CP1L
I/O memory
1 input word, 1 output word
(Allocated in the same way as for
other Expansion Units)
Node number
setting
Set using the DIP switch
(before the CPU Unit is turned ON.)
BD L NC(BS-) NC
BD H NC(BS+)
COMM
ERR
ON
123
4
5
6
No.
SRT21
EXP
CompoBus/S Master Unit
(or SRM1 CompoBus/S
Master Control Unit)
A maximum of 16 Units can be connected
(or 8 Units for CQM1-SRM21-V1).
CP1W-SRT21
CompoBus/S I/O Link Unit
CP1L
Special flat cable or VCTF cable
CS/CJ Series
C200H@ Series
CQM1(H) Series
SRM1 Series
CPM2C-S Series