Datasheet

G9SX-NS
25
LED Indicators
* Refer to “Fault Detection” on the next page for details.
Settings Indication (at Power ON)
Settings for the G9SX can be checked by the orange indicators for approx. 3 seconds after the power is turned ON. During this settings indication
period, the ERR indicator will light, however the auxiliary error output will remain OFF.
Marking Color Name G9SX-NS202
G9SX-
NSA222
G9SX-EX G9SX-EX-T Function
Reference
PWR Green
Power supply
indicator
❍❍❍❍Lights while power is supplied. ---
T1 Orange
Safety input #1
indicator
--- --- ---
Lights while a high signal is input to T12.
Flashes when an error relating to safety
input #1 occurs.
*
T2 Orange
Safety input #2
indicator
--- --- ---
Lights while a high signal is input to T22.
Flashes when an error relating to safety
input #2 occurs.
NS Orange
Non-contact Door
Switch input
indicator
❍❍--- ---
Lights when the Non-contact Door Switch
input turns ON. Flashes when an error
relating to the Non-contact Door Switch
input occurs.
FB Orange
Feedback/reset
input indicator
❍❍--- ---
Lights in the following cases:
With automatic reset while a high signal is
input to T33.
With manual reset while a high signal is
input to T32.
Flashes when an error relating to feedback/
reset input occurs.
AND Orange
Logical AND input
indicator
❍❍--- ---
Lights while a high signal is input to T41.
Flashes when an error relating to logical
AND connection input occurs.
EI Orange
Instantaneous
safety output
indicator
❍❍❍---
Lights while the Instantaneous safety
outputs (S14, S24, S34) are in the ON state.
Flashes when an error relating to the
instantaneous safety output occurs.
ED Orange
OFF-delayed
safety output
indicator
--- ---
Lights while OFF-delayed safety outputs
(S44, S54) are in the ON-state.
Flashes when an error relating to
OFF-delayed safety output occurs.
ERR Red Error indicator ❍❍❍❍Lights or flashes when an error occurs.
Indicator Item
Setting
position
Indicator
status
Setting mode Setting status
T1
Cross fault
detection
mode
Y1 terminal
Lit Detection mode Y1 = open
Not lit Non-detection mode Y1 = 24 VDC
FB Reset mode
T32 or T33
terminal
Lit Manual reset mode T33 = 24 VDC
Not lit Auto reset mode T32 = 24 VDC
AND
Logical AND
connection
input mode
Logical AND
connection
preset switch
Lit Enable logical AND input AND
Not lit Disable logical AND input OFF