Datasheet
3
D4E-@N
Approved Standard Ratings
UL/CSA
A300
TÜV (EN60947-5-1), CCC (GB14048.5)
Structure and Nomenclature
Voltage
Carry
current
Current (A) Volt-amperes (VA)
Make Break Make Break
120 V
240 V
10 A
60 A
30 A
6 A
3 A
7,200 720
Note: 1. @:Actuator variation of item II
2. AC-14 0.5 A/125 VAC means as follows:
3. Applicable category: AC-14
Rated operating current (I
e): 0.5 A
Rated operating voltage (U
e): 125 VAC
Model
Applicable category
and ratings
Thermal current
(Ithe)
Indicator
I II III IV
1
1
1
1
1
1
1
2
2
2
2
2
2
2
@
@
@
@
@
@
@
@
@
@
@
@
@
@
00
10
20, 21, 22
23, 24
23, 24
23, 24
23, 24
00
10
20, 21, 22
23, 24
23, 24
23, 24
23, 24
L
L1
L2
L3
L
L1
L2
L3
AC-14 0.5 A/125 VAC
DC-12 0.5 A/30 VDC
AC-15 2A/250 VAC
DC-12 2A/48 VDC
AC-15 2A/250 VAC
DC-12 2A/12 VDC
DC-12 2A/24 VDC
DC-12 2A/48 VDC
AC-14 0.1A/125 VAC
DC-12 0.1A/30 VDC
AC-14 0.1A/125 VAC
DC-12 0.1A/48 VDC
AC-14 0.1A/125 VAC
DC-12 0.1A/12 VDC
DC-12 0.1A/24 VDC
DC-12 0.1A/48 VDC
5 A
5 A
5 A
5 A
5 A
5 A
5 A
0.5 A
0.5 A
0.5 A
0.5 A
0.5 A
0.5 A
0.5 A
---
---
---
Neon lamp
LED
LED
LED
---
---
---
Neon lamp
LED
LED
LED
D4E-1
G
23 L N
I II III IV
C
haracter
i
st
i
cs
Degree of protection IP67
Durability *
Mechanical 10,000,000 operations min.
Electrical
500,000 operations min.
(5 A at 250 VAC, resistive load)
5,000,000 operations min.
(10 mA at 24 VDC, resistive load)
Operating speed 0.1 mm/sec to 0.5 m/sec
Operating frequency
Mechanical: 120 operations/min
Electrical: 30 operations/min
Rated frequency 50/60 Hz
Insulation resistance 100 MΩ min. (at 500 VDC)
Contact resistance
15 mΩ max. (initial value for the built-in switch when
tested alone)
Dielectric
strength
Between terminals of
same polarity
1,000 VAC, 50/60 Hz for 1 min
Between each terminal and non-
current-carrying metal part
1,500 VAC, 50/60 Hz for 1 min/Uimp at 2.5 kV
(EN60947-5-1)
Rated insulation voltage (Ui) 250V
Pollution degree (operating environment) 3 (EN60947-5-1)
Short-circuit protective device (SCPD) 10 A fuse (type gG or gI, IEC60269 approved)
Conditional short-circuit current 100 A (EN60947-5-1)
Conventional enclosed thermal current (Ithe) 5 A (EN60947-5-1)
Protection against electric shock
Class II (grounding not required with double insulation)
Vibration
resistance
Malfunction 10 to 55 Hz, 1.5-mm double amplitude
Shock
resistance
Destruction 1,000 m/s
2
max.
Malfunction 300 m/s
2
max.
Ambient operating temperature −10°C to +80°C (with no icing)
Ambient operating humidity 35% to 95%RH
Weight
Approx. 86 g (in case of roller plunger)
Eng
i
neer
i
ng Data
General-purpose Models
Electrical Durability (cosφ=1)
Operating temperature: +5
°
C to +30
°
C
Operating humidity: 40% to 70%RH.
3
1
1032 45678910
Switching current (A)
Durability (×10
4
operations)
Operating frequency: 30 operations/min
cosφ= 1
250 VAC
10
7
5
30
100
70
50
300
1,000
700
500
Note: 1. The above values are initial values.
2. The above ratings may vary depending on the
model. Contact your OMRON representative
for further details.
* Durability values are calculated at an operating
temperature of +5°C to +35°C, and an operating
humidity of 40% to 70%RH.
Movable Plunger
Rubber Cap (NBR)
· Rubber cap provides a tight seal and
ensures a long service life and
smooth reset at low temperatures.
Seal Packing (NBR)
Terminal Protection Cover
· D4E-@N has a wide wiring space of
10 mm horizontally.
Screw Terminal
· Screw terminal incorporates a M3 screw with a toothed washer.
Bearing
·
The bearing load strength has been increased to prevent faulty
resetting of the bearing, which may occur when the roller is
pressed with excessive force.
Die-cast Case
· Zinc die-cast case is anti-corrosive and tough.
Wiring Ease
· Wired made easier using
(D4CC-type) plug-in connector.
Built-in Switch
·
Prevents the movable piece from being pushed in too far, and
thereby contributes to a longer service life.
·
Switch cover ensures high insulation between the terminals
and die-cast. Double insulation means that grounding is
unnecessary. Meets UL, CSA, and EN standards.
· Seal packing withstands a pressure of 186 kPa.
S