Datasheet

G-157D4NL
Connections
Indicator
Internal Circuit Diagram
Circuit Connection Example
Terminals 12 and 41 are connected internally and so connect termi-
nals 11 and 42 for safety-circuit input. (GS-ET-19)
Connect terminals 21 and 22 and terminals 51 and 52 in series
when using as safety-circuit input (redundancy circuit for terminals
11 and 12 and terminals 41 and 42 above). Connect the terminals
individually when using as auxiliary-circuit input (e.g., terminals 21
and 22 for safety-door open/closed monitoring and terminals 51
and 52 for monitoring the lock status).
In the connection example on the right, terminals 21 and 22 and
terminals 51 and 52 are used as auxiliary-circuit input.
Direct opening contacts used as safety-circuit input are indicated
with the mark. Terminals 11 and 12 and terminals 21 and 22
are direct opening contacts.
Connect the indicators in parallel to the auxiliary circuits or termi-
nals E1 and E2.
If an indicator is connected in parallel to a direct opening contact,
when the indicator breaks, a short-circuit current will be generated,
possibly resulting in an installation malfunction.
Do not switch standard loads for more than 2 circuits at the same
time. Otherwise, the level of insulation may decrease.
The 24-VDC solenoid has polarity. Be sure to connect terminals
with the correct polarity.
D
R
R
LED
Z
10 to 115 VAC/VDC
Constant-current diode
42
11
21
33
E1 (+)
O1 O2
12 41
51
52
22
34
E2 ()
Indicator
(Orange)
Safety
circuit
Auxiliary
circuit
Auxiliary
circuit
Auxiliary
circuit