Datasheet

G2RV-SR
G2RV-SR G3RV-SR
Common AccessoriesCommon Precautions
6
Approved standards
UL508 (file No.E41643)
* If the load voltage exceeds 250 VAC, please attach with a spacing
of 12 mm min., or use a separate plate (XW5Z-EP12).
\TÜV (EN 61810-1)
* If the load voltage exceeds 250 VAC, please attach with a spacing
of 12 mm min., or use a separate plate (XW5Z-EP12).
Lloyd's (File No.07/10020)
Engineering Data
Endurance curve (N.O. side) Switching capacity of DC resistive load
Model Contact form Operation coil ratings Contact ratings Operations
G2RV-SR series
SPDT
12 to 48 VDC
24 to 230 VAC
6 A at 250 VAC (Resistive load)
6 A at 30 VDC (Resistive load)
2 A at 400 VAC (Resistive load)*
6,000
12 mm 12 mm 12 mm
Model Contact form Operation coil ratings Contact ratings Operations
G2RV-SR series
SPDT
12, 24 VDC
24, 48 VAC/VDC
100, 110, 200, 230 VAC
6 A at 250 VAC (Resistive load)
6 A at 30 VDC (Resistive load)
2 A at 400 VAC (Resistive load)*
50,000
50,000
6,000
12 mm 12 mm 12 mm
Model Contact form Operation coil ratings Contact ratings
G2RV-SR500
G2RV-SR700
SPDT
12, 24 VDC
24, 48 VAC/VDC
100, 110, 200, 230 VAC
6 A at 250 VAC (Resistive load)
2.5 A at 250 VAC (PF0.4)
6 A at 30 VAC (Ress)
2 A at 30 VDC (L/R=7ms)
G2RV-SR501
G2RV-SR701
SPDT
12, 24 VDC
24 VAC/VDC
6 A at 250 VAC (Resistive load)
2.5 A at 250 VAC (PF0.4)
6 A at 30 VAC (Ress)
2 A at 30 VDC (L/R=7ms)
G2RV-SR500-AP
G2RV-SR700-AP
SPDT
12, 24 VDC
24, 48 VAC/VDC
100, 110, 200, 230 VAC
0.05 A at 30 VAC (Resistive load)
0.05 A at 36 VDC (Resistive load)
10
100
1000
024
Opening and closing current (A)
6
250 VAC resistive load
30 VDC resistive load
30 VDC
inductive load
250 VAC
inductive
load
Number of operations (x 10
3
operations)
0.1
1.0
10.0
20 60 100 140 180 220
DC switching voltage (V)
DC breaking current (A)