Datasheet
Solid State Relays Common Precautions
■Application Circuit Examples
1. Connection to Sensors
The SSR connects directly to a Proximity Sensor or
Phot
oelectric Sensor.
2. Switching Control of Incandescent Lamps
3. Temperature Control of Electric Furnaces
4. Forward and Reverse Operation of Singlephase
Inductive Motors
Load
Load power supply
Sensor
(Brown)
(Black)
(Blue)
Sensors: TL-X Proximity Sensor
E3S Photoelectric Sensor
Load power supply
Incandescent
lamp
Input signal
source
Load power supply
Input signal
source and
Temperature
Controller
Load
heater
*
Load power supply
Motor
Note 1. The voltage between the load terminals of either SSR 1 or SSR
2 when turned OFF is approximately twice as high as the supply
voltage due to LC coupling. Be sure to use an SSR model with
a rated output voltage of at least twice the supply voltage.
For example, if the motor operates at a supply voltage of 100
VAC, the SSR must have an output voltage of 200 VAC or
higher.
Note 2. Make sure that there is a time lag of 30 ms or more to switch
over SW1 and SW2.
* Resistor to limit advanced phase capacitor discharge current.
To select a suitable resistor, consult with the manufacturer of the
motor.