Datasheet
G9SE
11
Use the following to wire to G9SE.
- Solid wire: AWG24 to AWG16 (0.25 to 1.5 mm
2
)
- Stranded wire: AWG24 to AWG16 (0.25 to 1.5 mm
2
)
- Strip the cover of wire no longer than 8 to 10 mm
When using stranded wire, insulated ferrule should be used. Use
below insulated ferrule.
But do not use ferrule terminals if G9SE is used as UL Listing. Insert
the strand or solid wire directly into the holes on the terminal block.
- Insulated ferrule: AWG24 to AWG16 (0.25 to 1.5 mm
2
)
- Crimp height(H): 2.0 mm max
Width(W): 2.7 mm max.
Conductor length: 8 to 10 mm
How to insert solid wire and insulated ferrule
The wire should be pushed into the terminal block straight. No need
to use the driver.
After inserting, make sure wire is fastened on to terminal block.
How to release wire
Use the following minus drive to release wire from terminal block.
And When releasing wire, the power source should be disconnected
1. Push the driver lightly into the taper of release hole.
2. Pull out the wire while the driver is pushed into release hole.
3. Pull out the driver.
Precautions for Correct wiring
Terminal block may be damaged.
1. Not push the driver into the release hole straight.
2. Not push the driver into the release hole by force of 30N and over.
3. Not tip or twist the driver pushed into release hole.
Certified Standards
EN ISO13849-1: 2008 PL e Safety Category 4,
IEC/EN 60947-5-1, IEC/EN 62061 SIL3,
EN 81-1, EN81-2,
UL508, CAN/CSA C22.2 No.14
GB 14048.5 (Scheduled to be certificated soon)
Safety category
In the conditions shown in '5.Examples of Application' , G9SE can be
used for the corresponding safety categories up to 4 and performance
level(PL) up to e per ISO13849-1.
This does NOT mean that G9SE can always be used for the required
category under all the similar conditions and situations.
Conformity to the categories must be assessed as a whole
system.When using G9SE for the safety categories, make sure the
conformity of the whole system.
Performance level and safety category
(EN ISO13849-1)
(1) Input the signals to both of the Safety inputs (T12 and T22)
(2) Input a signal to the Safety inputs (T11-T12 and T21-T22) through
switches with Direct Opening Mechanism. When using limit
switches, at least one of them must have Direct Opening
Mechanism.
And wiring must be done in a way that a short circuit between the
wires of Safety input can be prevented.
(3) When connecting Safety sensor with G9SE, use TYPE 4 safety
sensor.
(4) Input the signal through NC contacts of the contactors to
Feedback/Reset input (T31-T32 for manual reset or T31-T32 for
auto reset). (Refer to '5. Examples of Application')
(5) Be sure to connect the negative terminal of DC power supply to
ground.
(6) Use two Safety outputs (e.g. 13-14 and 23-24) to construct the
system.
Wiring
H
W
L
Recommended insulated ferrule:
manufactured by Phoenix contact
Type
Single
AI 0,34-8TQ
AI 0,5-10WH
AI 0,75-10GY
AI 1-10RD
AI 1.5-10BK
AI TWIN2x0.75-10GY
Twin
Wire size
Cross section (mm
2
)
AWG
0.34
0.5
0.75
1.0
1.5
2 × 0.75
22
20
18
18
16
Release hole
Wire
Recommended driver:
Type SZF0-0.4mmx2.5mm
manufactured by Phoenix contact
Type XW4Z-00B manufactured by Omron
Front
2.5 mm dia. max.
2.5 mm
Side
0.4 mm
8 to 12°
Driver
Standards