New Product Solid-state Timers H3DT DIN 17.5-mm-wide Slim Timers with Push-in Plus Technology for In-panel Applications * LR * CSA conformance evaluation by UL. • Helps save space and reduces work in control panels. • Slim Timers (17.5-mm width) with two sets of contacts: One of the slimmest Timers worldwide. *1 • Reduces power consumption (active power) by up to 60% to help reduce heat generation in control panels. *2 • Certified for maritime standards (LR/DNV GL). *3 • RoHS compliant *1.
Multi-range, Multi-mode Timer H3DT-N/H3DT-L * • Multiple time ranges and operating modes let you cover a wide range of applications. • The time-limit DPDT output contacts can be changed to timelimit SPDT and instantaneous SPDT output contacts using a switch. • Sequence checks are easily performed by setting an instantaneous output to 0. • Start signal control for some operating modes. LR * CSA conformance evaluation by UL.
H3DT-N/H3DT-L Specifications Time Ranges Time range setting Set time range 0.1 s 1s 10 s 1 min 10 min 1h 10 h 100 h 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to 120 min 1 to 12 h 10 to 120 h 100 to 1,200 h Scale numbers 12 Ratings Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2 Allowable voltage fluctuation range 85% to 110% of rated voltage Power reset Minimum power-OFF time: 0.1 s Reset voltage 10% of rated voltage Voltage input 24 to 240 VAC/DC High level: 20.
H3DT-N/H3DT-L Characteristics 1% of FS max. (1% 10 ms max. at 1.2-s range) Setting error 10% of FS 0.05 s max. Minimum input signal width 50 ms (start input) Influence of voltage 0.5% of FS max. (0.5% 10 ms max. at 1.2-s range) Influence of temperature 2% of FS max. (2% 10 ms max. at 1.2-s range) Insulation resistance 100 M min. at 500 VDC Dielectric strength Between charged metal part and operating section: 2,900 VAC 50/60 Hz for 1 min.
H3DT-N/H3DT-L Connections Block Diagrams H3DT-N/L Time setting detection circuit AC (DC) input ROM Time specification switches RAM Operating mode switch Clock Power supply circuit Output circuit One-chip microcomputer Input circuit Start input Indicator circuit Power indicator Output indicator Terminal Arrangement H3DT-N1/L1 H3DT-N2/L2 *2 A2 A1 B1 Start *2 A1 A2 B1 Start *1 R1 15 18 R1 15 16 18 *1. The *2.
H3DT-N/H3DT-L Input Connections The start input is a voltage input. PNP Transistor Input NPN Transistor Input Relay Input Voltage Input Signal Levels Sensor 24 VDC Sensor (sensor power supply) (+) 24 VDC (−) 24 VDC (sensor power supply) Timer A1 (+) B1 Start A2 (−) Operates when PNP transistor turns ON. 24 VDC Timer Timer A1 (−) A1 B1 Start B1 Start A2 (+) A2 (−) (+) Operates when NPN transistor turns ON. Transistor input Operates when relay turns ON.
H3DT-N/H3DT-L Dimensions (Unit: mm) Timers H3DT-N H3DT-L 17.5 17.5 90 H3DT-N2 H3DT-L2 100 H3DT-N1 H3DT-L1 H3DT-N2 H3DT-L2 H3DT-N1 H3DT-L1 86 5 90 Track Mounting Products (Sold Separately) Refer to page 29 for details. Options (Order Separately) Front Cover Refer to page 29 for details. Operating Procedures Basic Operation Setting Switches • Each switch has a snap mechanism that secures the switch at given positions. Set the switch to one of these positions.
H3DT-N/H3DT-L Timing Charts • There is no instantaneous output with the H3DT-N1/L1.
H3DT-N/H3DT-L E2: Interval (Power ON Start) Basic Operation t t− a t−a t Power (A1 and A2) Time-limit contacts: NC 15 and 16 (25 and 26) Time-limit contacts: NO (output indicator) 15 and 18 (25 and 28) Instantaneous contacts: NC (21 and 22) Instantaneous contacts: NO (21 and 24) Power Timing Output Operation / Power indicator E3: Signal OFF Interval t t−a t −a t t −a Basic Operation Power (A1 and A2) Start input (B1 and A1) Power Time-limit contacts: NC 15 and 16 (25 and 26) Start input Tim
H3DT-N/H3DT-L A: ON Delay (Signal ON Delay) t t−a Basic Operation t Power (A1 and A2) Start input (B1 and A1) Power Time-limit contacts: NC 15 and 16 (25 and 26) Start input Time-limit contacts: NO (output indicator) 15 and 18 (25 and 28) Instantaneous contacts: NC (21 and 22) Instantaneous contacts: NO (21 and 24) Timing Output * The start input is ignored while the Timer is in operation Operation / Power indicator B: Flicker OFF Start (Signal Start) t t t−a t t t Basic Operation t−a Pow
H3DT-N/H3DT-L E: Interval (Signal Start) t t t −a t −a t t−a Basic Operation Power (A1 and A2) Start input (B1 and A1) Power Time-limit contacts: NC 15 and 16 (25 and 26) Start input Time-limit contacts: NO (output indicator) 15 and 18 (25 and 28) Instantaneous contacts: NC (21 and 22) Instantaneous contacts: NO (21 and 24) Timing Output * The start input is valid while the Timer is in operation.
Power ON-delay Timer H3DT-A * • Single Mode Timers with power ON delay operation. LR * CSA conformance evaluation by UL. For the most recent information on models that have been certified for safety standards, refer to your OMRON website.
H3DT-A Characteristics 1% of FS max. (1% 10 ms max. at 1.2-s range) Setting error 10% of FS 0.05 s max. Influence of voltage 0.5% of FS max. (0.5% 10 ms max. at 1.2-s range) Influence of temperature 2% of FS max. (2% 10 ms max. at 1.2-s range) Insulation resistance 100 M min. at 500 VDC Dielectric strength Between charged metal part and operating section: 2,900 VAC 50/60 Hz for 1 min. Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min.
H3DT-A Connections Block Diagrams H3DT-A Time setting detection circuit AC (DC) input ROM Time specification switches Clock RAM Power supply circuit Output circuit One-chip microcomputer Indicator circuit Power indicator Terminal Arrangement H3DT-A1 H3DT-A2 * * A1 A2 R1 R1 R2 15 15 25 A2 A1 18 16 18 18 16 28 26 25 28 16 26 16 15 18 15 * The power supply terminals do not have polarity.
H3DT-A Nomenclature H3DT-A2 H3DT-A1 Front View Time range switch * Operation/power indicator (green) (Flashes while Timer is operating. Lit when Timer is stopped.) Main dial (for setting the time) Output indicator (orange) (Lit while Timer gives output.) Front View Time range switch * Operation/power indicator (green) (Flashes while Timer is operating. Lit when Timer is stopped.) Main dial (for setting the time) Output indicator (orange) (Lit while Timer gives output.
H3DT-A Operating Procedures Basic Operation Setting Switches • Each switch has a snap mechanism that secures the switch at given positions. Set the switch to one of these positions. Do not set it midway between two positions. Malfunction could result from an improper setting. Setting the Time Range Setting the Time Range The time range switch can be used to set the time range. Turn the switch with a flatblade or Phillips screwdriver.
Twin Timer H3DT-F * • Switch between flicker-OFF or flicker-ON start mode. • Independent ON time and OFF time settings. • Eight time ranges from 0.1 s to 1,200 h. LR * CSA conformance evaluation by UL. For the most recent information on models that have been certified for safety standards, refer to your OMRON website.
H3DT-F Characteristics 1% of FS max. (1% 10 ms max. at 1.2-s range) Setting error 10% of FS 0.05 s max. Influence of voltage 0.5% of FS max. (0.5% 10 ms max. at 1.2-s range) Influence of temperature 2% of FS max. (2% 10 ms max. at 1.2-s range) Insulation resistance 100 M min. at 500 VDC Dielectric strength Between charged metal part and operating section: 2,900 VAC 50/60 Hz for 1 min. Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min.
H3DT-F Connections Block Diagrams Terminal Arrangement H3DT-F H3DT-F * ON OFF indicator indicator AC (DC) input ON/OFF time setting detection circuit ON/OFF start switch A2 A1 Time specification switches Indicator circuit ROM RAM R1 Clock 15 One-chip microcomputer Power supply circuit Output circuit 18 16 16 18 15 (DIN notation) A1 A2 15 16 18 * The power supply terminals do not have polarity. Nomenclature H3DT-F Front View ON/OFF start switch (Default setting is for an OFF start.
H3DT-F Dimensions (Unit: mm) Timers H3DT-F 17.5 90 100 5 86 90 Track Mounting Products (Sold Separately) Refer to page 29 for details. Options (Order Separately) Front Cover Refer to page 29 for details.
Star-delta Timer H3DT-G * • Set two time ranges between 1 and 120 s with one Timer. LR * CSA conformance evaluation by UL. For the most recent information on models that have been certified for safety standards, refer to your OMRON website.
H3DT-G Characteristics 1% of FS max. Setting error 10% of FS 0.05 s max. Transfer time Total error (25% of transfer time + 5 ms) max. Influence of voltage 0.5% of FS max. Influence of temperature 2% of FS max. Insulation resistance 100 M min. at 500 VDC Dielectric strength Between charged metal part and operating section: 2,900 VAC 50/60 Hz for 1 min. Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min.
H3DT-G Connections Block Diagrams H3DT-G Terminal Arrangement AC (DC) input Power supply circuit H3DT-G Star-delta transfer time switch Star time setting switch * Star output ROM RAM Clock Output circuit A2 A1 Delta output One-chip microcomputer Star contacts Indicator circuit Star output ON Delta output ON indicator indicator Delta contacts R1 R2 15 25 18 16 28 26 25 28 26 16 18 15 (DIN notation) A1 A2 15 25 16 18 26 28 * The power supply terminals do not have polarity.
H3DT-G Dimensions (Unit: mm) Timers H3DT-G 17.5 90 100 5 86 90 Track Mounting Products (Sold Separately) Refer to page 29 for details. Options (Order Separately) Front Cover Refer to page 29 for details. Operating Procedures Basic Operation Setting the Time Ranges Setting the Time Setting the Delta Time Range (t1) and the Star-delta Transfer Time (t2) Setting the Time The start time is set with the main dial.
Power OFF-delay Timer H3DT-H * • Set two time ranges with each Timer, from 0.1 to 12 seconds for the S Series and from 1.0 to 120 seconds for the L Series. LR * CSA conformance evaluation by UL. For the most recent information on models that have been certified for safety standards, refer to your OMRON website.
H3DT-H Characteristics 1% of FS max. (1% 10 ms max. at 1.2-s range) Setting error 10% of FS 0.05 s max. Influence of voltage 0.5% of FS max. (0.5% 10 ms max. at 1.2-s range) Influence of temperature 2% of FS max. (2% 10 ms max. at 1.2-s range) Insulation resistance 100 M min. at 500 VDC Dielectric strength Between charged metal part and operating section: 2,900 VAC 50/60 Hz for 1 min. Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min.
H3DT-H Connections Block Diagrams Terminal Arrangement H3DT-H H3DT-H * AC (DC) input Indicator circuit Time specification switches A2 A1 Power supply circuit Oscillation circuit Counting circuit Output circuit R1 15 Power interruption detection circuit 18 16 16 18 15 (DIN notation) A1 A2 15 16 18 Note: The above figure shows the terminal arrangement for a 24 to 48-VAC/DC model. Models with 100 to 120-VAC or 200 to 240-VAC power input do not have a DC input.
H3DT-H Dimensions (Unit: mm) Timers H3DT-H 17.5 90 100 5 86 90 Track Mounting Products (Sold Separately) Refer to page 29 for details. Options (Order Separately) Front Cover Refer to page 29 for details. Operating Procedures Basic Operation Setting the Time Setting the Time Ranges Setting the Time Ranges Setting the Time The scale multiplier can be changed with the timer range switch. It can be changed between 0.
H3DT Track Mounting Products (Sold Separately) (Unit: mm) DIN Track PFP-100N PFP-50N 7.3±0.15 4.5 35±0.3 15 25 10 25 25 10 1,000 (500) * 27±0.15 15(5) * 25 1 * Dimensions in parentheses are for the PFP-50N. DIN Track PFP-100N2 16 4.5 35±0.3 27 15 25 10 25 25 10 1,000 End Plate PFP-M 25 15 24 29.2 1 1.5 10 6.2 50 M4x8 panhead screw 1.8 1 35.5 35.3 1.8 11.5 10 1.3 4.8 M4 screw and washer Spacer PFP-S 16 12 5 34.8 44.3 16.5 Note: 1.
H3DT Safety Precautions Refer to Safety Precautions for All Timers. Format of Warning Indications CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage. Precautions for Safe Use Indicates supplementary comments on what to do or avoid doing, to use the product safety.
H3DT • The Timer may not operate properly in locations that are subject to sulfide gas, such as in sewers or incinerators. Products that are suitable for operation in sulfide gas are not available for OMRON Timers or general control devices. Seal the Timer to isolate it from sulfide gas. If the Timer cannot be sealed, OMRON can make special products with resistance to sulfide gas for some Timers. Ask your OMRON representative for details.
H3DT • If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not be different in phase or the terminals will be short-circuited to one another. Always use the same power supply phases. Wiring 1.
H3DT 2. Removing Wires from the Push-In Plus Terminal Block Recommended Flat-blade Screwdriver Use the following procedure to remove wires from the terminal block. The same method is used to remove stranded wires, solid wires, and ferrules. 1. Hold a flat-blade screwdriver at an angle and insert it into the release hole. 2. With the flat-blade screwdriver still inserted into the release hole, remove the wire from the terminal insertion hole. 3. Remove the flat-blade screwdriver from the release hole.
H3DT Other Precautions • If the Timer is mounted on a control panel, dismount the Timer from the control panel before carrying out a voltage withstand test between the electric circuits and non-current-carrying metal parts of the Timer. (Otherwise, the internal circuits of the Timer may be damaged.) • The H3DK-H uses a latching relay for the output. Shock, such as dropping the H3DK-H during shipment or handling, can cause the output contacts to reverse to the neutral position.
Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron).
OMRON Corporation Industrial Automation Company Authorized Distributor: Kyoto, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 2895 Greenspoint Parkway, Suite 200 Hoffman Estates, IL 60169 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No.