20 Multifunction Counter H7BX
When the H7BX using as a tachometer, switch to the tachometer configuration using the procedure given on page 23.
■ Settings for Advanced Functions
Settings that cannot be performed with the DIP switch are performed with the operation keys.
(See note 2.)
(See note 1.)
Tachometer
output mode
(TOTM)
Prescale
value
(PSCL)
NPN/PNP
input mode
(IMOD)
Display
color
(COLR)
Key protect
level
(KYPT)
(No decimal
point)
(One digit
after decimal
point)
(Two digits
after decimal
point)
(Three digits
after decimal
point)
Decimal
point
position
(DP)
Counting
speed
(CNTS)
(30 Hz) (10 kHz)
(PNP
input)
(NPN
input)
(99.9 s)(0.0 s)
(99.9 s)(0.1 s)
(99.999)(1.000)(0.001)
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5)
(Green)(Red) (Red-green) (Green-red)
Average
processing
(AVG)
Auto-zero
time
(AUTZ)
Startup
time
(STMR)
The characters displayed in reverse video are the initial values.
When performing settings with operation keys only, turn ON pin 1 of the DIP switch to OFF (factory setting). If
pin 1 of the DIP switch is ON, the setting items indicated by will not be displayed.
3 s min.3 s min.
(No average
processing)
(Average
of 2
measurements)
(Average
of 4
measurements)
(Average
of 8
measurements)
Up
Up
Up
Up
Up
Up
Up
Up
Up
Up
Power ON
Run modeFunction setting mode
(AREA) (HI-HI) (LO-LO)(HI-LO)
• Set the tachometer output mode with any of the Keys.
• Set the number for each digit with the Keys.
• Set the NPN/PNP input mode with any of the Keys.
• Set the display color with any of the Keys.
• Set the key protect level with any of the Keys.
• Set the average processing with any of the Keys.
• Set the number for each digit with the Keys.
• Set the number for each digit with the Keys.
• Set the counting speed with any of the Keys.
• Set the decimal point position with any of the Keys.
Note: 1. If the mode is switched to the function setting mode during operation, operation will
continue.
2. Changes made to settings in function setting mode are enabled for the first time when
the mode is changed to run mode. Also, when settings are changed, the counter is
automatically reset (measured values initialized and outputs turned OFF) on returning
to run mode.
For details on operations in run mode, refer to page 22.