Datasheet
K8AK-PH
2
Ratings and Specifications
Ratings
Rated input voltage 3-phase, 200 to 480 VAC (3-wire)
Input load Approx. 4.1 VA
Operating time
Phase sequence 0.1 s±0.05 s
Phase loss 0.1 s max. (when the voltage changes rapidly from 100% to 0% of rated voltage)
Reset method Automatic reset
Indicators Power (PWR): Green, Relay output (RY): Yellow
Output relays One DPDT relay (NC operation)
Output relay ratings
Rated load
Resistive load
5 A at 250 VAC
5 A at 30 VDC
Minimum load: 24 VDC, 4 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations
3 A at 250 VAC/30 VDC:100,000 operations
Ambient operating temperature −20 to 60°C (with no condensation or icing)
Storage temperature −25 to 65°C (with no condensation or icing)
Ambient operating humidity 25% to 85% (with no condensation)
Storage humidity 25% to 85% (with no condensation)
Altitude 2,000 m max.
Terminal screw tightening torque 0.49 to 0.59 N·m
Terminal wiring method
Recommended wire
Solid wire: 2.5 mm
2
Twisted wires: AWG16, AWG18
Note: 1. Ferrules with insulating sleeves must be used with twisted wires.
2. Two wires can be twisted together.
Recommended ferrules
Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact
Al 1-8RD (for AWG18) manufactured by Phoenix Contact
Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact
Case color N1.5
Case material PC and ABS, UL 94 V-0
Weight Approx. 130 g
Mounting Mounts to DIN Track.
Dimensions 22.5 × 90 × 100 mm (W×H×D)