Datasheet
K8AK-PH
9
1. Do not use or store the product in the following locations.
• Locations subject to water or oil
• Outdoor locations or under direct sunlight
• Locations subject to dust or corrosive gases (particularly
sulfurizing gases, ammonia, etc.)
• Locations subject to rapid temperature changes
• Locations prone to icing and dew condensation
• Locations subject to excessive vibration or shock
• Locations subject to wind and rain
• Locations subject to static electricity and noise
• Habitats of insects or small animals
2. Use and store the product in a location where the ambient
temperature and humidity are within the specified ranges. If
applicable, provide forced cooling.
3. Mount the product in the correct direction.
4. Do not wire the input and output terminals incorrectly.
5. Make sure the input voltage and loads are within the
specifications and ratings for the product.
6. Make sure the crimp terminals for wiring are of the specified size.
7. Do not connect anything to terminals that are not being used.
8. Use a power supply that will reach the rated voltage within 1
second after the power is turned ON.
9. Keep wiring separate from high voltages and power lines that
draw large currents.
Do not place product wiring in parallel with or in the same path as
high-voltage or high-current lines.
10.Do not install the product near equipment that generates high
frequencies or surges.
11.The product may cause incoming radio wave interference. Do not
use the product near radio wave receivers.
12.Install an external switch or circuit breaker and label it clearly so
that the operator can quickly turn OFF the power supply.
13.Make sure the indicators operate correctly. Depending on the
application environment, the indicators may deteriorate
prematurely and become difficult to see.
14.Do not use the product if it is accidentally dropped. The internal
components may be damaged.
15.Be sure you understand the contents of this catalog and handle
the product according to the instructions provided.
16.Do not install the product in any way that would place a load on it.
17.When discarding the product, properly dispose of it as industrial
waste.
18.The product must be handled only by trained electrician.
19.Prior to operation, check the wiring before you supply power to
the product.
20.Do not install the product immediately next to heat sources.
21.Perform periodic maintenance.
Observe the following operating
methods to prevent failure and
malfunction.
1. Use the input power and other power supplies and converters
with suitable capacities and rated outputs.
2. The distortion in the input waveform must be 30% max. If the
input waveform is distorted beyond this level, it may cause
unnecessary operation.
3. The product cannot be used for thyristor control or on the
secondary side of an inverter. To use the product on the
secondary side of an inverter, install a noise filter on the primary
side of the inverter.
4. Phase loss is detected only when the power supply to the motor is
turned ON. Phase loss during motor operation is not detected.
5. When cleaning the product, do not use thinners or solvents. Use
commercial alcohol.
Mounting and Removing
• Mounting to DIN Track
1. Catch the upper hook on the DIN Track.
2. Push the product onto the Track until the hooks lock into place.
• Removing from the DIN Track
Pull down on the bottom hook with a flat-blade screwdriver and lift
up on the product.
Precautions for Safe Use Precautions for Correct Use
AB
PFP-100N (100 cm)
PFP-50N (50 cm)
Applicable DIN Tracks: