Datasheet

General-purpose Relays MK-S New Model 3
Specifications
Ratings
Coil Ratings
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for AC rated current and
±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. The maximum voltage is one that is applicable instantaneously to the Relay coil at 23°C and not continuously.
4. For DC-operated Relays with the LED indicator built-in, add an LED current of approx. 5 mA to the rated current.
Contact Ratings
Rated voltage Rated current Coil resistance Must operate
voltage
Must release
voltage
Max. voltage Power
consumption
50 Hz 60 Hz
AC 6 V 443 mA 385 mA 3.1 80% max. of rated
voltage
30% min. of rated
voltage at 60 Hz
25% min. of rated
voltage at 50 Hz
110% of rated volt-
age
Approx. 2.3 VA
at 60 Hz
Approx. 2.7 VA
at 50 Hz
12 V 221 mA 193 mA 13.7
24 V 110 mA 96.3 mA 48.4
100 V 26.6 mA 23.1 mA 760
110 V 24.2 mA 21.0 mA 932
200 V 13.3 mA 11.6 mA 3,160
220 V 12.1 mA 10.5 mA 3,550
230 V 10.0 mA 11.5 mA 4,250
240 V 11.0 mA 9.6 mA 4,480
DC 6 V 224 mA 26.7 15% min. of rated
voltage
Approx. 1.4 W
12 V 112 mA 107
24 V 55.8 mA 430
48 V 28.1 mA 1,710
100 V 13.5 mA 7,390
110 V 12.3 mA 8,960
Load Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4)
Contact mechanism Single
Contact material AgSnIn
Rated load NO 10 A, 250 VAC
10A, 30 VDC
7 A, 250 VAC
NC 5 A, 250 VAC
5 A, 30 VDC
Rated carry current 10 A
Max. switching voltage 250 VAC, 250 VDC
Max. switching current 10 A
Max. switching power NO 2,500 VA/300 W
NC 1,250 VA/150 W