The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Voltage Input Signal Levels
No-contact Input No-contact Input Contact Input
Sensor
Timer
Start
Operates with PNP transistor ON
Operates with NPN transistor ON
Timer
Sensor
Timer
Operates with relay ON
Voltage Inputs
Input 0V
Start
Input 0V
Start
Input 0V
AC power supply
DC power supply
(Connection to PNP open
collector output sensor)
12 to 24 VDC
(sensor power supply)
DC power
supply
Power
supply (+)
Power
supply
()
(Connection to NPN open
collector output sensor)
12 to 24 VDC
(sensor power supply)
DC power
supply
Power
supply (+)
Power
supply ()
Note: The input circuit is isolated from the
power supply circuit. Thus, an NPN
transistor can be connected.
Power
supply (+)
Power
supply ()
Note: Refer to the signal levels in the
following table and be aware of the
minimum applicable load of the relay.
No-contact
input
1. Transistor ON
Residual voltage: 1 V max.
The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF
Leakage current: 0.01 mA max.
The voltage between terminals 6 and 7 must be 1.2 VDC max.
Contact
input
Use contacts that can adequately switch 0.1 mA at each
operating voltage.
The voltage between terminals 6 and 7 with contacts ON or
OFF must satisfy the specified value.
Contacts ON
100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC
or 85 to 137.5 VDC
24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF
100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or
0 to 10 V
DC
24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
Note: Before making connections, refer to Safety Precautions (H3CR-
@
).