Datasheet

H3CR-G
36
Specifications
General
Note: For details, refer to your OMRON website.
Time Ranges
Ratings
Note: 1. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
2. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
Item H3CR-G8L H3CR-G8EL
Functions Star-delta timer Star-delta timer with instantaneous output
Pin type 8-pin
Operating/Reset method Time-limit operation/Self-reset
Output type Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Instantaneous: SPST-NO
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
Time unit Star operation time ranges
Scale number (max.)
6Set time range0.5 to 6 s
12 1 to 12 s
60 5 to 60 s
120 10 to 120 s
Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s, or 1.0 s
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-opening time: 0.5 s
Power consumption 100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC
Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy