Correct Installation Method
For installation, to improve the long time reliability of the UPS, pay
much attention to heat dissipation. Ensure convection of air around
the UPS main body, and use the UPS in an operating condition
below the derating curve.
During machining work for mounting, make sure that no metal
scrap goes into the product.
The heat dissipation of the UPS may become worse depending on
how the UPS is mounted; in rare cases, internal components may
deteriorate and get damaged. Use the UPS in an operating
condition based on the derating curve for each mounting direction.
Standard mounting (Mounting to the DIN rail)
Stationary mounting
Face-up mounting
Incorrect Installation Method
Mounting to the DIN Track
Stationary installation
Battery Replacement
The UPS supports hot swapping. Battery replacement is possible
both when the power is turned OFF (while the power output is OFF)
and when the power is turned ON (while the power output is ON).
To install devices other than the UPS to both sides, install them by leaving
a space specified by each device off the UPS.
Leave space of 50 mm above and below
Leave space of 50 mm above and below
To mount UPS on floor with its back side away
from you, mount it so that its back side is in contact
with wall.(Because PCB is partially exposed in its
back side, and UPS may be affected by static
electricity for that reason.)
To mount UPS on floor with its top side away from
you, mount it so that its top side is 50 mm or more
off wall.
Mount UPS upside down
DIN Track is placed vertically
Do not stackDo not mount on floor with
front side down
To mount UPS on floor with its top side away
from you, ensure that its top side is not in
contact with wall.