New Product Switch Mode Power Supply S8JX-G Series S8JX-G S8JX (15/35/50/100/150/300/600-W Models) Easy-to-use, Widely range from 15 W to 600 W (Output Voltage: 5 V to 48 V) S8JX-P • Easy Mounting: Front-mounted type, DIN rail-mounted type are available. Screw-mount at the top. (except 300-/600-W models) • Safety standards: UL 508/60950-1 cUL CSA C22.2 No. 107.1 cUR CSA C22.2 No. 60950-1 EN 50178 (= VDE 0160) Over voltage category III EN 60950-1 (= VDE 0805 Teil 1) • EMC: Conforms to EN 61204-3.
S8JX Model Number Structure Model Number Legend Note: Not all combinations are possible. Refer to List of Models in Ordering Information on page 3. S8JX-G 15-/35-/50-/100-/150-W Models S8JX-G@@@@@@@ 1 1. Power Ratings 015: 15 W 035: 35 W 050: 50 W 100: 100 W 150: 150 W 2. Output Voltage 05: 5 V 12: 12 V 15: 15 V 24: 24 V 48: 48 V 2 3 4 3. Configuration (15/35/50/100/150 W model) None: Open-frame C: Covered 4.
S8JX Ordering Information List of Models Note: For details on normal stock models, contact your nearest OMRON representative. Input voltage Power ratings 15 W 35 W Front-mounting *1 50 W 100 W (80 to 370 VDC *3) S8JX-G15005@: Switchable between 100 to 120 VAC and 200 to 240 VAC. (DC power cannot be input.) Open-frame Power Supplies 150 W 15 W 35 W 50 W 100 W 150 W *1. The front-mounting bracket is included as standard with the product. *2.
S8JX Configuration Input voltage Power ratings S8JX-G 15 W 35 W Front-mounting *1 50 W 100 W 100 to 240 VAC (free) S8JX-P (80 to 370 VDC *3) S8JX-G15005@@: Switchable between 100 to 120 VAC and 200 to 240 VAC. (DC power cannot be input.
S8JX Ratings, Characteristics, and Functions Input specification 35 W 68% min. 80 to 370 VDC *9 Frequency *2 Current *3 50/60 Hz (47 to 450 Hz) 100 V input 0.4 A max. 200 V input 0.25 A max. Power factor Inrush current (for a cold start at 25°C) *3 1 A max. 0.6 A max. --- Harmonic current emissions Leakage current *3 73% min. 100 to 240 VAC (allowable range: 85 to 264 VAC) Voltage *2 --- 100 V input 0.5 mA max. 200 V input 1 mA max. 100 V input 20 A max. 200 V input 40 A max.
S8JX Input specification S8JX-G Efficiency S8JX-P Output *4 100 W 76% min. 76% min. 12-V Models 81% min. 81% min. 24-V Models 83% min. 83% min. 48-V Models 82% min. 83% min. 100 to 240 VAC (allowable range: 85 to 264 VAC) 80 to 370 VDC *9 Frequency *2 Current *3 50 W 5-V Models Voltage *2 Input 100 to 240 V input Power ratings *1 Item 50/60 Hz (47 to 450 Hz) 100 V input 1.4 A max. 200 V input 0.8 A max. Power factor 2.5 A max. 1.5 A max.
S8JX Input specification Power ratings *1 Item Efficiency Voltage *2 Frequency *2 Current *3 Input Power factor Harmonic current emissions 100 V input Leakage current *3 200 V input 100 V input Inrush current (for a cold start at 25°C) *3 200 V input Noise filter Voltage adjustment range *5 Ripple *3 Input variation influence Load variation influence Temperature variation influence Startup time Hold time *3 Overload protection *6 80 to 370 VDC *9 3.6 A max. 2.2 A max. 3.5 A max. 2.1 A max. ----- 0.
S8JX Input specification 100/200 V (Selected) Power ratings *1 Item S8JX-G Efficiency 300 W 600 W 5V models 71% min. 72% min. 12V models 75% min. 78% min. 24V models 82% min. 80% min. 48V models 82% min. 80% min. Voltage *2 100 to 120 VAC (allowable range: 85 to 132 VAC) 200 to 240 VAC (allowable range: 170 to 264 VAC) (Switchable) Frequency *2 50/60 Hz (47 to 450 Hz) 100 V input 8 A max. 16 A max.(5V, 12V, 48V) 14 A max.(24V) 200 V input 4.5 A max. 9 A max.
S8JX S8JX-G *1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not start. Refer to Overload Protection on page 19. *2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *3. Rated input voltage: 100 or 200 VAC at 100% load. *4.
S8JX Connections Block Diagrams S8JX-G S8JX-G01505@@ (15 W) S8JX-G01512@@ (15 W) S8JX-G01515@@ (15 W) S8JX-G01524@@ (15 W) AC (L) INPUT +V Fuse 2.0 A Noise filter DC OUTPUT −V AC (N) Inrush current protection Rectifier Smoothing circuit Rectifier/ Smoothing circuit Drive control Circuit Overcurrent detection circuit Voltage detection Overvoltage detection circuit Photocoupler S8JX-G01548@@ (15 W) S8JX-P +V AC (L) INPUT Fuse: 2.
S8JX AC (L) INPUT +V Fuse 6.3 A Noise filter DC OUTPUT −V AC (N) Inrush current protection Rectifier Smoothing circuit Rectifier/ Smoothing circuit S8JX-G S8JX-G05005@@ (50 W) S8JX-G05012@@ (50 W) S8JX-G05024@@ (50 W) Drive control Circuit Overcurrent detection circuit Voltage detection Overvoltage detection circuit Photocoupler S8JX-G05048@@ (50 W) +V AC (L) Fuse: 6.
S8JX S8JX-G15005@@ (150 W) S8JX-G Rectifier/ smoothing circuit +V AC (L) Fuse: 8A INPUT Noise filter DC OUTPUT −V AC (N) Rectifier/ smoothing circuit Inrush current protection Drive control circuit Overcurrent detection circuit Voltage detection circuit Overvoltage detection circuit Photocoupler Input voltage switch 100/200 V switching Note: Set the input voltage switch to "115V" for 100 to 120 VAC and to "230V" for 200 to 240 VAC.
S8JX S8JX-G30024@@ (300 W) S8JX-G30048@@ (300 W) +V Fuse 10 A INPUT Noise filter DC OUTPUT −V AC (N) Inrush current protection Rectifier/ Smoothing circuit S8JX-G Rectifier/ Smoothing circuit AC (L) 100/200V (Selectable) Drive control Circuit Overcurrent detection circuit Voltage detection Overvoltage detection circuit Photocoupler Parallel operation selector S8JX-P Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC.
S8JX Construction and Nomenclature Nomenclature 15-/35-/50-/100-/150-W Models S8JX-G No. D E D E A +V −V C C B −V AC (L) B AC (N) 2 AC Input Terminals (L), (N) Connect the input lines to these terminals. *1 3 Protective Earth Terminal (PE) ( Connect the ground line to these terminals. *2 4 Output Voltage Adjuster (V. ADJ) It is possible to increase or decrease the output voltage. 5 Output Indicator (DC ON: Green) Lights green while a direct current (DC) output is ON.
S8JX 600-W 5V, 12V Model 600-W Model −V −V +V +V Side AC (L) 2 AC Input Terminals (L), (N) Connect the input lines to these terminals. *1 3 Protective Earth Terminal (PE) ( Connect the ground line to these terminals. *2 4 Input Voltage Selector Terminals Short-circuit the terminals if the input is 100 to 120 VAC and open the terminals if the input is 200 to 240 VAC. 5 Output Indicator (DC ON: Green) Lights green while a direct current (DC) output is ON. 6 Output Voltage Adjuster (V.
S8JX Engineering Data Derating Curves (Standard Mounting) 15-/35-/50-/100-/150-W Models Covered Power Supplies 120 100 A Load rate (%) Load rate (%) S8JX-G Open-frame Power Supplies 120 100 80 80 60 60 40 40 20 20 0 −20 −10 0 10 20 0 −20 −10 30 40 50 60 70 80 Ambient Temperature (°C) A 0 10 20 30 40 50 60 70 80 Ambient Temperature (°C) S8JX-P Note: 1. Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.
S8JX Mounting 15-/35-/50-/100-/150-W Models S8JX-G The following three mounting methods are possible. . Front-mounting: Refer to Mounting Bracket Provided with Front-mounting Power Supplies . Bottom-mounting . Side-mounting Note: Additional mounting methods are also available using DIN Rail-mounting models. on page 25. B C Standard Mounting 15-/35-/50-/100-/150-W Models Front-mounting Bottom-mounting DIN Rail-mounting Vertical Side-mounting Horizontal Side-mounting * S8JX-P * * * Note: 1.
S8JX 600-W Model S8JX-G Front-mounting 20mm min. Side-mounting S8JX-P Common Precautions 18 Bottom-mounting 20mm min. 20mm min. 20mm min. Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the standard mounting method only. 2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended. 3.
S8JX Overload Protection S8JX-G The Power Supply is provided with an overload protection function that protects the power supply from possible damage by overcurrent. When the output current rises above 105% to 175% min. of the rated current, the protection function is triggered, decreasing the output voltage. When the output current falls within the rated range, the overload protection function is automatically cleared. Note: 1.
S8JX Overvoltage Protection 15-/35-/50-/100-/150-W Models S8JX-G Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback circuit in the power supply fails. When an excessive voltage that is approximately 130% of the rated voltage or more is output, the output voltage is shut OFF, preventing damage to the load due to overvoltage.
S8JX Dimensions (Unit: mm) Front-mounting Models Panel mounting holes dimensions 5 max. 90±1 10 max. Surface screw mounting Label 9.5 Two, M3 3.5 8.2 S8JX-G S8JX-G015@@ (15 W) S8JX-G015@@C (15 W) S8JX-G035@@ (35 W) S8JX-G035@@C (35 W) Side Mounting 91±1 75±0.5 75±0.5 82±0.5 Five, M3.5 3.5 dia. Two, M3 Cover 35.5±1 39.5±1 4.5 82±0.5 8.5 78±0.5 Bottom Mounting 7.5 78±0.5 3.5 3.5 dia. 26.5 S8JX-P 17.5 Two, M3 (Depth 4 mm max.) 50±0.
S8JX S8JX-G15005 (150 W) S8JX-G15005C (150 W) S8JX-G Panel mounting holes dimensions 12max. 2-M4 Label 5max. 178±1 Surface screw mounting 10 Two, M3 3.5 13 9.5 8.2 92±1 Side Mounting 68±0.5 68±0.5 3-M3.5 169±0.5 3.5 dia. Two, M3 Cover 60±1 8 169±0.5 5 5 Two, M3 (Depth: 4 mm max.) 3.5 dia. Bottom Mounting 169±0.5 169±0.5 3.5 S8JX-P 33.5 36 14 140±0.5 Input voltage switch S8JX-G15012 (150 W) S8JX-G15012C (150 W) Panel mounting holes dimensions 10max. 178±1 5max.
S8JX S8JX-G30005C (300 W) S8JX-G30012C (300 W) 22.5 max. Five, M4 terminal screws Panel mounting holes dimensions Surface screw mounting 164.5 ±1 Four, 4.5 dia. Side Mounting 10 26 13 92±1 8.6 16 S8JX-G Four, M5 terminal screws Eight, M4 holes (depth: 8 max. on both sides) 50±0.5 50±0.5 136±0.5 Four, 4.5 dia. 21 17 110±1 136±0.5 Bottom Mounting 90±0.5 136±0.5 S8JX-P 90±0.5 Four, M4 holes (depth: 8 max.) 10 17 S8JX-G30024C (300 W) S8JX-G30048C (300 W) Eight, M4 holes (depth: 8 max.
S8JX S8JX-G60005@ (600 W) S8JX-G60012@ (600 W) S8JX-G Panel mounting holes dimensions Eight, M4 holes (depth: 8 max. on both sides) 150±1 Four, M5 terminal screws 16 24.4±0.5 26 13 Surface screw mounting 159.8±1 Four, 4.5 dia. Side Mounting 92±1 50±0.5 124±0.5 50±0.5 Four, 4.5 dia. 20.9 Bottom Mounting Five, M4 terminal screws 8.6 10 124±0.5 11 100±0.5 137±0.5 S8JX-P Four, M4 holes (depth: 8 max.) 100±0.5 42 137±0.5 14.
S8JX Mounting Bracket Provided with Front-mounting Power Supplies a 15-/35-/50-/100-/150-W Models Front-mounting Method Mounting dimensions Dimensions 1.5 4.6 15±0.2 11 9 Two, M3 Note: Mounting screws are not provided. Temporarily attach the enclosed mounting bracket as shown in the illustration on the right, hook the holes (parts a) in the Power Supply on hooks on the mounting bracket (parts b), and secure the Power Supply with two mounting screws. b a 60 60 Two, 3.5 dia.
S8JX Separately purchasable mounting brackets (Please ask your dealer for details of delivery.) For 15-W/30-W/50-W/100-W/150-W/300-W/600-W models (separately purchasable) S8JX-G Bracket for changeover from S82J-series The mounting-hole pitch of mounting brackets A - I below is identical to that of our product S82J. These brackets can be used for switchover with the S82J-series.
S8JX Å@ Mounting Bracket C S82Y-JX15B S8JX-G Method of Mounting 188 178±0.5 3 R0.5 4.5 dia. R2.25 4.5 50 35 B R2 Thickness = 2 A · A Mounting Bracket D S82Y-JX15F S8JX-P Screws used A: Accessories (2 locations) Be sure to use the accessory screws. Mounting screw tightening torque (recommended): 0.49 N m B: M4 (2 locations) B Method of Mounting 45 54 45.6 4.5 25 B 5 dia.
S8JX Mounting Bracket F S82Y-JX30B S8JX-G Method of Mounting 167 150±0.1 7 Four, M4 110 Front 100±0.1 A B A A B Screws used A: Accessories (4 locations) Be sure to use the accessory screws. B: M4 (4 locations) Screws of a length that will not project beyond the fixture (thickness: 3.2 mm) should be selected. B Thickness = 3.2 Mounting Bracket G S82Y-JX30F 10 dia. R2.5 Method of Mounting 29.6 S8JX-P 11.6 A 7.5 7.5 A 145±0.3 160 A 145±0.3 A Two, 5 dia. 92 Thickness = 1.
S8JX DIN Rail-mounting Models 14.5 max. 6 max. 44±1 90±1 10 max. S8JX-G S8JX-G015@@D (15 W) S8JX-G015@@CD (15 W) S8JX-G030@@D (35 W) S8JX-G030@@CD (35 W) Label 5 max. 9.5 8.2 91±1 Five, M3.5 47 Cover 98.6 7 (Sliding: 16.6 max.) 6 max. 44±1 14.5 max. 100±1 10 max. S8JX-P S8JX-G050@@D (50 W) S8JX-G050@@CD (50 W) Label 9.5 5 max. 8.2 92±1 47 Five, M3.5 Cover 36±1 108.6 7 (Sliding: 16.6 max.) 40±1 10 max. 6 max. 50±1 100 W 150±1 150 W 14.5 max. 100·150 W 5 max. Label 9.5 8.
S8JX S8JX-G15005D (150 W) S8JX-G15005CD (150 W) 6 max. 2-M4 14.5 max. 60±1 12 max. 5 max. 178±1 S8JX-G Label 10 13 9.5 8.2 92±1 47 3-M3.5 Cover 7 (Sliding: 16.6 max.) 186.6 S8JX-P Input voltage switch S8JX-G15012D (150 W) S8JX-G15012CD (150 W) 6 max. 14.5 max. 60±1 10 max. 178±1 5 max. Label 9.5 8.2 92±1 47 5-M3.5 Cover Common Precautions 30 186.6 7 (Sliding: 16.6 max.
S8JX S8JX-G30005CD (300W) S8JX-G30012CD (300W) 22.5 max. 7.5 175.3±1 10 26 13 92±1 8.6 16 S8JX-G Five, M4 terminal screws Four, M5 terminal screws 46.6 4.4 (Sliding: 10 max.) 179.3 6.5 max. 6.5 max. 110±1 S8JX-P Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail. S8JX-G30024CD (300 W) S8JX-G30048CD (300 W) 4 max. (17.7) Nine, M4 terminal screws 20 max. 167.1±1 10.2 8.6 92±1 46.6 4.4 (Sliding: 10 max.) 6.5 max. 110±1 6.5 max. 181.
S8JX DIN Rail (Order Separately) S8JX-G Mounting Rail (Material: Aluminum) 7.3±0.15 4.5 35±0.3 15 25 10 25 25 1,000 (500) ∗ 15 (5) * 25 10 27±0.15 Model PFP-100N PFP-50N 1 * Value in parentheses are for PFP-50N. Mounting Rail (Material: Aluminum) 16 4.5 35±0.3 27 24 29.2 Model PFP-100N2 15 25 25 10 25 1,000 10 25 End Plate 15 1 1.5 10 S8JX-P 6.2 M4 × 8 panhead screw 1.8 1 50 1.8 35.5 35.5 Model 11.5 PFP-M 10 M4 spring washer 1.3 4.8 Note: 1.
S8JX Model Number Structure Model Number Legend Note: Not all combinations are possible. Refer to List of Models in Ordering Information on page 34. S8JX-P@@@@@@@ 1 1. Power Ratings 050: 50 W 100: 100 W 150: 150 W 2. Output Voltage 05: 5 V 12: 12 V 24: 24 V 48: 48 V 2 3 4 3. Configuration (50/100/150 W model) None: Open-frame C: Covered 4. Configuration/mounting None: Front-mounting D: DIN Rail-mounting S8JX-G 50-/100-/150-W Models 300-/600-W Models 1 1. Power Ratings 300: 300 W 600: 600 W 2 3 2.
S8JX Ordering Information List of Models Note: For details on normal stock models, contact your nearest OMRON representative.
S8JX Configuration Input voltage Power ratings Output voltage (VDC) 24 V 600 W 24 V 300 W 24 V 600 W 24 V 300 W 24 V 600 W 24 V Front-mounting *1 Covered Power SupDIN Rail-mounting *2 plies 100 to 240 VAC (free) (80 to 370 VDC *3) Without mounting brackets *2 Model S8JX-P30024C Upcoming S8JX-P60024C Upcoming S8JX-G 300 W Output current 14 A peak current 16.5 A (200 VAC) 27 A peak current 31 A (200 VAC) 14 A peak current 16.
S8JX Ratings, Characteristics, and Functions Input specification S8JX-G Efficiency S8JX-P Output *4 50 W 100 W 150 W 5-V Models 73% min. 78% min. 79% min. 12-V Models 76% min. 78% min. 78% min. 24-V Models 77% min. 81% min. 81% min. 48-V Models 80% min. 81% min. 82% min. Voltage *2 100 to 240 VAC (allowable range: 85 to 264 VAC) Frequency *2 50/60 Hz (47 to 63 Hz) Current *3 Input 100 to 240 V input Power ratings *1 Item 80 to 370 VDC *9 100 V input 0.75 A max. 1.4 A max.
S8JX Input specification 24V models Frequency *2 600 W 78% min. 50/60 Hz (47 to 63 Hz) 100 V input 4.5 A max. 8.7 A max. 200 V input 2.2 A max. 4.3 A max. Power factor Output *4 79% min. 100 to 240 VAC (allowable range: 85 to 264 VAC) 80 to 370 VDC *8 Voltage *2 Current *3 300 W 0.9 min. Harmonic current emissions Conforms to EN61000-3-2 Leakage current *3 100 V input 0.5 mA max. 200 V input 1 mA max. Inrush current (for a cold start at 25°C) *3 100 V input 17.5 A max.
S8JX S8JX-G S8JX-P Common Precautions 38 *1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not start. Refer to Overload Protection on page 44. *2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *3. Rated input voltage: 100 or 200 VAC at 100% load. *4.
S8JX Connections Block Diagrams S8JX-P050@@@@ (50 W) +V Fuse 2.5 A Noise filter DC OUTPUT AC(N) –V Rectifier High-frequency current regulation Inrush current protection Smoothing circuit Rectifier/ Smoothing circuit S8JX-G AC(L) INPUT Drive control Circuit Overcurrent detection circuit Voltage detection Overvoltage detection circuit Photocoupler AC(L) INPUT +V Fuse 6.
S8JX S8JX-P300@@@@ (300 W) S8JX-G ALM Alarm display Fan detection AC(L) Fuse 10 A INPUT ALMC Noise filter Alarm output ALME Photocoupler AC(N) Rectifier Inrush current High-frequency Smoothing protection current regulation circuit Alarm detection +V DC OUTPUT -V Rectifier/ Smoothing circuit Drive circuit Control circuit +V Output voltage monitor -V Overcurrent detection circuit +S Remote sensing Rectifier/ Smoothing circuit Auxiliary power supply circuit Voltage detection Overheating d
S8JX Construction and Nomenclature Nomenclature 50-/100-/150-W Models 5 4 1 1 –V –V 3 2 3 AC(L) 2 AC Input Terminals (L), (N) Connect the input lines to these terminals. *1 3 Protective Earth Terminal (PE) ( Connect the ground line to these terminals. *2 4 Output Voltage Adjuster (V. ADJ) It is possible to increase or decrease the output voltage. 5 Output Indicator (DC ON: Green) Lights green while a direct current (DC) output is ON.
S8JX Engineering Data Derating Curves (Standard Mounting) 50-/100-W Models 120 1 100 150-W Models Front-mounting, DIN Rail mounting, Bottom-mounting Load rate (%) Load rate (%) S8JX-G Front-mounting, DIN Rail mounting, Bottom-mounting, Side-mounting 120 1 100 80 80 Covered type 60 Covered type 60 Open-frame type Open-frame type 40 40 20 20 0 –20 –10 0 10 20 S8JX-P Note: 1. Internal parts may occasionally deteriorate or be damaged.
S8JX Mounting 50-/100-/150-W Models S8JX-G The following three mounting methods are possible. . Front-mounting: Refer to Mounting Bracket Provided with Front-mounting Power Supplies on page 52. . Bottom-mounting . Side-mounting Note: Additional mounting methods are also available using DIN Rail-mounting models. B C Standard Mounting 50-/100-/150-W Models DIN Rail-mounting Front-mounting Bottom-mounting Vertical Side-mounting Horizontal Side-mounting * * S8JX-P * * Note: 1.
S8JX S8JX-G Remote sensing function Alarm detection function This function is used when compensating the voltage drop of the load line. The remote sensing function is operated by connecting +S terminal (2 pin on CN) to +side of the load terminal and -S terminal (4 pin on CN) to -side of the load terminal.
S8JX Overvoltage Protection Overheat Protection 50-/100-/150-W Models 300-/600-W Models If the internal temperature rises excessively as a result of fan failure or any other reason, the overheat protection circuit will be triggered to shut OFF the output voltage and simultaneously the protection-ON alarm indicator will be lit. Reset the input power by turning it OFF for at least three minutes and then turning it back ON again.
S8JX Dimensions (Unit: mm) Front-mounting Models S8JX-G S8JX-P050@@ (50 W) S8JX-P050@@C (50 W) 129±1 11.5 max. Panel mounting holes dimensions 5 max. Surface screw mounting Label 9.5 3.5 (for mounting) 8.2 Two, M3 Side Mounting 78.5±0.5 92±1 Five, M3.5 78.5±0.5 118±0.5 Cover 42±1 Two, M3 3.5 dia. (for mounting) 5 Bottom Mounting 7 118±0.5 120±0.5 5 120±0.5 3.5 (for mounting) 3.5 dia. (for mounting) 36 S8JX-P Two, M3 (Depth 4 mm max.
S8JX S8JX-P15005 (150 W) S8JX-P15005C (150 W) 5 max. Label 13 Panel mounting holes dimensions 10 3.5 (for mounting) Surface screw mounting S8JX-G 159±1 13.5 max. Two, M4 Two, M3 78.5±0.5 92±1 8.2 Side Mounting 78.5±0.5 9.5 Three, M3.5 Cover 42±1 3.5 dia. (for mounting) 5 148±0.5 7 148±0.5 Two, M3 5 150±0.5 3.5 (for mounting) 3.5 dia. (for mounting) Bottom Mounting 150±0.5 36 15 Two, M3 (Depth 4 mm max.) 98±0.
S8JX S8JX-P300@@C (300 W) S8JX-G 70±1 48±0.5 Two, 4.5 dia. 5 Panel mounting holes dimensions Four, M5 26 13 Rear surface screw mounting 113.5±0.5 110.8±1 Three, M4 48±0.5 16 Three, 4.5 dia. 8.5 10 4.5 13.5 Front Mounting 214.3 239.8 max. 77.6±1 113.5±0.5 S8JX-P S8JX-P300@@N (300 W) 22.5 max. 165±1 Four, M4 (Depth 6 mm max.) 71±1 Panel mounting holes dimensions Rear surface screw mounting 26 13 92±1 16 Four, M5 24.1 8.5 Three, M4 Common Precautions 48 Four, 4.5 dia. 46±0.
S8JX S8JX-P600@@C (600 W) 98±0.5 26 13 Four, M5 Two, 4.5 dia. Panel mounting holes dimensions Rear surface screw mounting 16 5 93±0.5 Three, 4.5 dia. S8JX-G 109±1 110.8±1 113.5±0.5 Three, M4 Front Mounting 13.5 10 214.3 4.5 8.5 113.5±0.5 239.8 max. 116.6±1 S8JX-P S8JX-P600@@N (600 W) 22.5 max. 110±1 26 16 164.8±1 Four, M4 (Depth 6 mm max.) 13 Panel mounting holes dimensions Four, M5 Rear surface screw mounting Standard Mounting 21 64±0.5 Three, M4 10 125±0.5 25 8.5 112±0.
S8JX DIN Rail-mounting Models S8JX-G S8JX-P050@@D (50 W) S8JX-P050@@CD (50 W) 11.5 max. 6 max. 14.5 max. 129±1 43.4±1 Label 9.5 5 max. 8.2 92±1 47 Five, M3.5 Cover S8JX-P S8JX-P100@@D (100 W) S8JX-P100@@CD (100 W) S8JX-P15012D (150 W) S8JX-P15012CD (150 W) S8JX-P15024D (150 W) S8JX-P15024CD (150 W) S8JX-P15048D (150 W) S8JX-P15048CD (150 W) 7 (Sliding: 16.6 max.) 137.6 42±1 14.5 max. 43.4±1 6 max. 11.5 max. 159±1 5 max. Label 9.5 8.2 92±1 47 Five, M3.5 Cover 167.
S8JX S8JX-P300@@CD (300 W) 5.5 70±1 S8JX-G Four, M5 26 13 Three, M4 110.8±1 16 8.5 46 10 6.6 (Sliding: 12 max.) 77.6±1 214.3 9.1 239.8 max. Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail. Four, M5 109±1 26 13 S8JX-P S8JX-P600@@CD (600 W) 5.5 16 110.8±1 46 10 Three, M4 8.5 6.6 (Sliding: 12 max.) 214.3 239.8 max. Note: Use a metal DIN Rail when mounting a 600-W model to a DIN Rail. Common Precautions 116.
S8JX Mounting Bracket Provided with Front-mounting Power Supplies a S8JX-G S82Y-J00F Front-mounting Bracket Front-mounting Method Mounting dimensions Dimensions 1.5 4.6 15±0.2 11 9 Two, M3 Note: Mounting screws are not provided. Temporarily attach the enclosed mounting bracket as shown in the illustration on the right, hook the holes (parts a) in the Power Supply on hooks on the mounting bracket (parts b), and secure the Power Supply with two mounting screws. b a 60 60 Two, 3.5 dia.
S8JX Safety Precautions Refer to Safety Precautions for All Power Supplies. Minor electric shock, fire, or Product failure may occasionally occur. Do not disassemble, modify, or repair the Product to touch the interior of the Product. S8JX-G CAUTION 15-/35-/50-/100-/150-W Models Standard Mounting (Front-mounting and DIN Rail-mounting) Standard Mounting (Bottom-mounting) *1 *1 Minor burns may occasionally occur.
S8JX S8JX-P Series 300-W Models S8JX-G For S8JX-P Series 300-/600-W models, PHD connectors manufactured by JST Mfg. Co., Ltd. should be used. *1 *1 *3 S8JX-G Series 600-W Models *1 *1 *3 S8JX-P Series 600-W Models S8JX-P *1 *1 *1. Convection of air *2. 20 mm min. (15 mm min. for S8JX-P series) *3. Use a metal plate as the mounting surface. Wiring Common Precautions • Connect the ground completely. A protective earthing terminal stipulated in safety standards is used.
S8JX Output Voltage Adjuster (V.ADJ) Parallel Operation 15-/35-/50-/100-/150-W Models S8JX-G • The output voltage adjuster (V.ADJ) may possibly be damaged if it is turned with unnecessary force. Do not turn the adjuster with excessive force. • After completing output voltage adjustment, be sure that the output capacity or output current does not exceed the rated output capacity or rated output current. The Product is not designed for parallel operation.
S8JX Switching the AC Input Voltage between 100 and 200 VAC S8JX-P Series 300-/600-W Models S8JX-G Connecting CB terminal (5 pin on CN) and CBG terminal (6 pin on CN) enables the current balancing function and that allows the parallel operation at 80% or less of the total output capacity. Up to five Power Supplies can be connected. • Use 2-conductor shielded cable as a connection wire (*1).
S8JX Fan Replacement S8JX-G Series 300-W 5V, 12V/600-W Model • Please contact your OMRON sales representative regarding fan replacement. Fans will be replaced at cost. In addition, a replacement fan unit (Model S82Y-JXP@@FAN) is available. Please use the curve below as a guideline for the timing of fan replacement. • Fan replacements made by the customer fall outside the scope of safety standards. Replacement should be implemented as shown below.
S8JX Typical Values For Reference Only S8JX-G Series S8JX-G Power ratings Item Efficiency 150 W 300 W 79% 80% 81% 83% 75% 78% 84% 85% 86% 85% 80% 83% 15-V models 80% 84% --- --- --- --- --- 24-V models 81% 84% 86% 88% 90% 88% 84% 80% 84% 86% 89% 91% 88% 85% 0.19 A 0.43 A 0.6 A 1.1 A 2.0 A 3.7 A 6.5 A 0.30 mA 0.30 mA 0.35 mA 0.30 mA 0.60 mA 0.7 mA 0.6 mA 40 A 40 A 40 A 37 A 42 A 35 A 35 A 5-V models 0.35% (p-p) 0.35% (p-p) 0.60% (p-p) 1.
Read and Understand this Catalog Please read and understand this catalog before purchasing the product. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON Corporation Industrial Automation Company Authorized Distributor: Tokyo, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC One Commerce Drive Schaumburg, IL 60173-5302 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No.