New Product Switch Mode Power Supply S8VK-T (120/240/480/960 W Models) Worldwide 3-phase Power Supply Resistant in tough environments Easy and fast installation The most compact class on the market • Wide input range for worldwide applications: 380 to 480 VAC (320 to 576 VAC) • Possible for 2-phase input usage*: 380 to 480 VAC (340 to 576 VAC) *When using the 960 W at 2-phase input, the power rating is 768 W.
S8VK-T Specifications Ratings, Characteristics, and Functions Power rating Item Efficiency 3-phase, 400 VAC input *11 Frequency *1 Current Reliability Construction 3.5 mA max./1.4 mA typ. Inrush current (for a cold start at 25C) *2 3-phase, 400 VAC input 28 A typ. 29 A typ. Rated output current 5A 10 A Boost current 6A 12 A Voltage adjustment range *3 22.5 to 29.5 VDC (with V.ADJ) (guaranteed) Ripple & Noise voltage *4 160 mV p-p max.
S8VK-T Power rating Item Efficiency 3-phase, 400 VAC input *11 Voltage range *1 Input Frequency *1 Current Reliability Construction 3-phase, 380 to 480 VAC (allowable range: 320 to 576 VAC) 2-phase, 380 to 480 VAC (allowable range: 340 to 576 VAC) 450 to 600 VDC (allowable range: 450 to 810 VDC) *8 3-phase, 380 to 480 VAC (allowable range: 320 to 576 VAC) 2-phase, 380 to 480 VAC (allowable range: 340 to 576 VAC) 1.2 A typ. 2.1 A typ. - 3.5 mA max./1.2 mA typ. 3.5 mA max./1.0 mA typ.
S8VK-T *1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *2. For a cold start at 25C. Refer to Engineering Data on page 7 to 8 for details. *3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 29.5 VDC of the voltage adjustment range.
S8VK-T Connections Block Diagrams S8VK-T12024 (120 W) S8VK-T24024 (240 W) L1 +V INPUT L2 L3 DC OUTPUT Noise filter Rectifier lnrush Smoothing current circuit protection Rectifier/ smoothing circuit −V Drive control circuit Voltage detection circuit Overcurrent detection circuit Overvoltage detection circuit Photocoupler S8VK-T48024 (480 W) S8VK-T96024 (960 W) L1 +V INPUT L2 L3 DC OUTPUT Noise filter Rectifier lnrush Smoothing current circuit protection Rectifier/ smoothing circuit −V D
S8VK-T Construction and Nomenclature Nomenclature 120 W Model 240 W Model 480 W Model S8VK-T12024 S8VK-T24024 S8VK-T48024 3 1 3 4 4 4 5 5 5 1 2 2 1 2 3 960 W Model S8VK-T96024 4 5 1 2 3 6 No. 1 2 3 4 5 6 *1. *2. *3. *4. 6 Name Input terminals (L1), (L2), (L3) Protective Earth terminal (PE) / Ground DC Output terminals (V), (+V) Output indicator (DC ON: Green) Output voltage adjuster (V.
S8VK-T Engineering Data 120 W (S8VK-T12024) 960 W (S8VK-T96024): Standard mounting Load ratio (%) Load ratio (%) Derating Curve 120 100 A B 80 C 120 B A 80 60 60 40 40 20 20 0 −40 −25 C 100 0 −40 −10 0 10 20 30 40 50 60 70 80 −25 Ambient temperature (°C) Note: Ambient temperature (°C) This is the guaranteed value for startup. (3-phase only) Note: A. Standard mounting B. Face-up mounting at 480 VAC or lower or 678 VDC or lower C.
S8VK-T Overvoltage Protection (A) Standard (Vertical) mounting (B) Face-up mounting Overload Protection Output voltage (V) The load and the power supply are automatically protected from overcurrent damage by this function. Overload protection is activated if the output current rises above 121% of the rated current. When the output current returns within the rated range, overload protection is automatically cleared.
S8VK-T Dimensions (Unit: mm) S8VK-T12024 (120 W) 122.2±1 (1) 40±1 117.8 112.2 6.35 (4) 104.6 125±1 6.35 4.7 (Sliding: 7.5 max.) Rail Stopper 19.8 S8VK-T24024 (240 W) (10) 150±1 (1) 60±1 145.6 140 6.35 104.6 (4) 125±1 6.35 4.7 (Sliding: 7.5 max.) Rail Stopper 19.8 (10) 150±1 (1) S8VK-T48024 (480 W) 145.6 140 95±1 (4) 125±1 52.3 6.35 6.35 19.8 (26.8) 30 4.7 (Sliding: 7.5 max.) (10) Rail Stopper 25 S8VK-T96024 (960 W) (1) 135±1 180±1 175.6 170 (4) 125±1 47.9 10.
S8VK-T DIN Rail (Order Separately) Note: All units are in millimeters unless otherwise indicated. Mounting Rail (Material: Aluminum) PFP-100N PFP-50N 7.3±0.15 4.5 35±0.3 15 25 10 25 25 10 1,000 (500) * 25 27±0.15 15(5) * 1 * Values in parentheses are for the PFP-50N. Mounting Rail (Material: Aluminum) PFP-100N2 16 4.5 35±0.3 27 15 25 10 25 25 10 1,000 25 15 24 29.2 1 1.5 End Plate PFP-M 10 6.2 M4×8 panhead screw 1.8 1 50 1.8 35.5 35.5 11.5 10 M4 spring washer 1.3 4.
S8VK-T Mounting Brackets Name Model Qty used Front-mounting bracket (for 120, 240 and 480 W models) S82Y-VK10F 1 Front-mounting bracket (for 960 W model) S82Y-VK10F 2 Side-mounting bracket (for 120 W model) S82Y-VK10S 1 Side-mounting bracket (for 240 W model) S82Y-VK20S 1 Note: Be sure to use the accessory screws. Mounting screw tightening torque (recommended): 4.43 to 5.31 lb-in (0.5 to 0.6 N·m) Type Model Dimensions Appearance 120 W model 240 W model For 960W type 4-4.5 dia.±0.
S8VK-T Safety Precautions Warning Indications CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction or undesirable effect on product performance.
S8VK-T Precautions for Safe Use Wiring Connect the ground completely. A protective earthing terminal stipulated in safety standards is used. Electric shock or malfunction may occur if the ground is not connected completely. Minor fire may possibly occur. Ensure that input and output terminals are wired correctly. Do not apply more than 75-N force to the terminal block when tightening it.
S8VK-T Mounting Power Boost Function Take adequate measures to ensure proper heat dissipation to increase the long-term reliability of the Product. Be sure to allow convection in the atmosphere around devices when mounting. Do not use in locations where the ambient temperature exceeds the range of the derating curve. When cutting out holes for mounting, make sure that cuttings do not enter the interior of the Products.
S8VK-T The outputs are floating outputs (i.e., the primary circuits and secondary circuits are separated). You can therefore make positive and negative outputs by using two Power Supplies. You can make positive and negative outputs with any of the models. If positive and negative outputs are used, connect Power Supplies of the same model as in the following figure. (Combinations with different output capacities or output voltages can be made.
S8VK-T Backup Operation In Case There Is No Output Voltage Backup operation is possible if you use two Power Supplies of the same model. Even if one Power Supplies fails, operation can be continued with the other Power Supply. Make sure that the maximum load does not exceed the capacity of one Power Supply. For backup operation, connect the S8VK-R for 120 W, 240 W, and 480 W. Refer to the S8VK-R datasheet (Catalog No.: T059) for S8VK-R specifications and the model number for each capacity.
S8VK-T Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance The recommended replacement period for preventive maintenance is greatly influenced by the application environment of the product. As a guideline, the recommended replacement period is 7 to 10 years.* To prevent failures or accidents that can be caused by using a product beyond its service live, we recommend that you replace the product as early as possible within the recommended replacement period.
Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron).
OMRON Corporation Industrial Automation Company Authorized Distributor: Kyoto, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 2895 Greenspoint Parkway, Suite 200 Hoffman Estates, IL 60169 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No.