Datasheet

S8VK-X
21
Mounting
Wiring
Connect the ground completely. A protective earthing terminal
stipulated in safety standards is used. Electric shock or malfunction
may occur if the ground is not connected completely.
Minor fire may possibly occur. Ensure that input and output
terminals are wired correctly.
When you insert wires or insert a screwdriver into a release hole,
do not press down on the terminal block with a force of 40 N or
greater.
Do not wire anything to the release holes.
Do not tilt or twist a flat-blade screwdriver while it is inserted into a
release hole on the terminal block. The terminal block may be
damaged.
Insert a flat-blade screwdriver into the release holes at an angle.
The terminal block may be damaged if you insert the screwdriver
straight in.
Do not allow the flat-blade screwdriver to fall out while it is inserted
into a release hole.
Do not bend a wire past its natural bending radius or pull on it with
excessive force. This may cause a wire to be broken.
Do not insert more than one wire into each terminal insertion hole.
Do not pre-solder the ends of the wires. Doing so will inhibit proper
connection.
Be sure to remove the sheet covering the S8M for machining
before power-ON so that it does not interfere with heat dissipation.
If there is a possibility of vibration or shock, please use wires and
stranded wires with ferrules.
Use the following material for the wires after confirming the rating
of the wires in order to prevent smoking or ignition.
Recommended Wire Type
Input crossover wiring can be used for the input side of this Power
Supply.
Do not use crossover wiring for more than five Power Supplies,
and do not allow the steady-state current to the input terminals to
exceed 10 A. The above table gives the recommended wires for
one Power Supply.
If you use crossover wiring for N number of Power Supplies, a
current that is N times the current for a standalone Power Supply
may flow to the input terminals.Take this into consideration when
you select wiring materials.
Stripping Length
S8VK-X03005-EIP, S8VK-X06012-EIP,
S8VK-X06024-EIP, S8VK-X09024@-EIP,
S8VK-X12024@-EIP, S8VK-X24024@-EIP
: Input and output terminals
S8VK-X48024@-EIP: Input terminals
S8VK-X48024@-EIP: Output terminals
(A) Standard (vertical)
mounting
(B) Front, side-by-side
mounting
Terminal Model number
Recommended wire
gauge
(mm
2
) (AWG)
Input
S8VK-X03005-EIP,
X06012-EIP, X06024-EIP,
X09024@-EIP, X12024@-EIP
0.34 to 2.5 22 to 14
S8VK-X24024@-EIP 0.5 to 2.5 20 to 14
S8VK-X48024@-EIP 0.75 to 2.5 18 to 14
Output
S8VK-X03005-EIP 0.75 to 2.5 18 to 14
S8VK-X06012-EIP 0.75 to 2.5 18 to 14
S8VK-X06024-EIP 0.5 to 2.5 20 to 14
S8VK-X09024@-EIP 0.5 to 2.5 20 to 14
S8VK-X12024@-EIP 0.75 to 2.5 18 to 14
S8VK-X24024@-EIP 2 to 2.5 14
S8VK-X48024@-EIP 3.5 to 6 12 to 10
PE
(protective
earth)
terminal
S8VK-X03005-EIP,
X06012-EIP, X06024-EIP,
X09024@-EIP, X12024@-EIP,
X24024@-EIP, X48024@-EIP
2 to 2.5 14
Recommended wire
gauge
Stripping length
(Ferrules not used)
0.34 to 1.5 mm
2
/
AWG22 to 16
8 mm
2 to 2.5 mm
2
/AWG14 10 mm
Recommended wire
gauge
Stripping length
(Ferrules not used)
3.5 to 6 mm
2
/
AWG12 to 10
15 mm