Datasheet

S8VK-X
7
Communication and Indication Items
Note: For details on the communication function and setting method, refer to the Switch Mode Power Supply S8VK-X Communication Manual
(Man. No. T213).
* Communication cycle can be set from 100 to 10,000 ms. The indication update cycle is 50 ms.
Inrush Current, Startup Time, and Output Hold Time
Note: Twice the normal inrush current will flow during parallel operation or for backup operation. Also, if crossover wiring is used for N number of
Power Supplies, an inrush current of N times the inrush current for a standalone Power Supply will flow. Therefore, check the fusing
characteristics of fuses and operating characteristics of breakers making sure that the external fuses will not burn out and the circuit breakers
will not be activated by the inrush current.
Item
Communication
*
Indication
monitor *
Resolution
Data update
cycle
Details
Output voltage measurement Yes Yes 0.1 V 5 ms
Measurement accuracy
±2% (percentage of output voltage value)
±1 digit
Output current measurement Yes Yes 0.1 A 5 ms
Measurement accuracy
±5% (percentage of rated output current)
±1 digit
Peak hold current measurement Yes Yes 0.1 A 5 ms
Measurement accuracy
±5% (percentage of rated output current)
±1 digit
Years until replacement Yes Yes 0.1 years 1 min
Range
0.0 to 15.0 years (communication)
FUL (Full) / HLF (Half) /
0.0 to 4.9 years (indication monitor)
Percentage until replacement Yes Yes 0.1% 1 min
Range
0.0 to 100%
Total run time Yes Yes
Communication 1 h
1 min
Range
0 to 262,800 h (communication)
0 to 263 kh (indication monitor)
Indication monitor 1 kh
Continuous run time Yes None 1 min 1 min
Range
0 to 15,768,000 min
Self-diagnostics Yes Yes None None
Refer to Self-Diagnostics Function on
page 11 for details.
Product model Yes None None None Product model is expressed in ASCII code
Serial number Yes None None None Expressed in hexadecimal (4-byte)
Firmware version Yes None None None Expressed in hexadecimal (2-byte)
MAC address Yes None None None None
IP address Yes None None None None
IP address setting method Yes None None None Static IP address/BOOTP selection
Startup time
Hold time
AC input voltage
AC input current
Output voltage
Inrush current on input application
90
96.5%
Input ON
Input OFF