Datasheet

XW5T
7
Feed Through Terminal Blocks
Model XW5T-S4.0-2.2-1(BL) XW5T-S4.0-1.1-2 XW5T-S4.0-1.1-2V
Appearance and internal wiring
1 tier, 2:2 2 tiers, 1:1 2 tiers, 1:1
Applicable wire sizes
NOMINAL CROSS SECTION 4.0 mm
2
4.0 mm
2
4.0 mm
2
Minimum conductor cross section solid
0.14 mm
2
0.14 mm
2
0.14 mm
2
Maximum conductor cross section solid
6.0 mm
2
6.0 mm
2
6.0 mm
2
Minimum
conductor
cross section fine
stranded
0.14 mm
2
0.14 mm
2
0.14 mm
2
Maximum
conductor
cross section fine
stranded
6.0 mm
2
6.0 mm
2
6.0 mm
2
Minimum conductor cross section (flex.,
stranded) with cable end sleeve
0.5 mm
2
0.5 mm
2
0.5 mm
2
Maximum conductor cross section (flex.,
stranded) with cable end sleeve
4.0 mm
2
4.0 mm
2
4.0 mm
2
Conductor cross section AWG AWG26 to AWG10 AWG26 to AWG10 AWG26 to AWG10
Wire strip length 9 mm 9 mm 9 mm
Tightening torque 0.5 Nm 0.5 Nm 0.5 Nm
Dimensions 6×69×58 6×73×75 6×73×75
Mounting rail TH35 TH35 TH35
IEC rated voltage 500 V 800 V 800 V
IEC rated current 32 A 32 A 32 A
Rated impulse voltage 6 kV 8 kV 8 kV
UL rated voltage 300 V 300 V 300 V
UL rated current 30 A 30 A 30 A
End Covers XW5E-S4.0-2.2-1 XW5E-S4.0-1.1-2 XW5E-S4.0-1.1-2
Applicable nameplates XW5Z-4.0LB@ XW5Z-4.0LB@ XW5Z-4.0LB@
Applicable Short Bars
XW5S-S4.0-@
(@: Poles = 2, 3, 4, 5, or 10)
XW5S-S4.0-@
(@: Poles = 2, 3, 4, 5, or 10)
XW5S-S4.0-@
(@: Poles = 2, 3, 4, 5, or 10)