User's Manual
Table Of Contents
- Read and Understand this Manual
- Warranty
- Limitations of Liability
- Suitability for Use
- Programmable Products
- Change in Specifications
- Dimensions and Weights
- Errors and Omissions
- Applicable Standards
- Applicable SEMI Standards
- Precautions for Safe Use
- Precautions for Correct Use
- Editor’s Note
- Table of Contents
- What is a CIDRW System?
- Features
- System Configuration
- Component Names and Functions
- Flowchart for Getting Started
- Installation
- Connections and Wiring
- Set the Communications Conditions for the CIDRW Controller
- Set the Communications Conditions for Amplifier Units
- Set the Communications Conditions for Link Units
- Communications Test
- When SECS is Used
- When SECS is Not Used
- When SECS is Used
- When SECS is Not Used
- Specifications and Dimensions
- Data Segment Area
- Regular Inspection
- SECS Protocol Specifications
- ASCII Code Table
- Protective Construction
77
CIDRW System
User’s Manual
SECTION 4
When SECS is Used
SECTION 4
Reading from/Writing to ID Tags
• Subsystem command (ChangeState)
S18,F13 Subsystem Command Request (ChangeState) S,H→E,reply
L,3
1.<TARGETID> "00" (fixed)
2.<SSCMD> "ChangeState"
3.L,1
1.<CPVAL1> "OP", "MT" or "PS"
CPVAL = "PS" is a parameter setting unique to this CIDRW Controller for switching to the Setting mode.
S18,F14 Subsystem Command Acknowledge (ChangeState) S,H←E
L,3
1.<TARGETID> "00"
2.<SSACK>
3.L,s
1.<STATUS1>
⋅
s.<STATUSs>
• When the specified target is invalid:
s = 0, SSACK = "CE" communications error
• When SSCMD is invalid:
s = 0, SSACK = "CE" communications error
• When OperationalStatus is BUSY:
s = 0, SSACK = "EE" execution error
• If the status of SSACK is other than "NO" (normal), the List of Status will comprise zero items.