Network Card User Manual

22
Performance Specifications
Item
CJ2H-
CPU64-EIP CPU65-EIP CPU66-EIP CPU67-EIP CPU68-EIP
Communications
Logical Ports for
Communications
Logical Ports 8 ports (Used for SEND, RECV, CMND, PMCR, TXDU, and RXDU instructions.)
Extended Logical Ports 64 ports (Used for SEND2, RECV2, CMND2, and PMCR2 instructions.)
Cip
Communications
Specification
Class 3
(Number of Connections)
Number of connections: 64
UCMM
(Non-connection Type)
Maximum number of clients that can communicate at the same time: 32
Maximum number of servers that can communicate at the same time: 40
Peripheral (USB) Port USB 2.0-compliant B-type connector
Baud Rate 12 Mbps max.
Transmission Distance 5 m max.
Serial Port Interface: Conforms to EIA RS-232C.
Communications Method Half-duplex
Synchronization Method Start-stop
Baud Rate 0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 (kbps)
Transmission Distance 15 m max.
EtherNet/IP Port
Transmission Specifications
Media Access Method CSMA/CD
Modulation Baseband
Transmission Paths Star
Baud Rate 100 Mbps (100Base-TX)
Transmission Media Shielded twisted-pair (STP) cable; Categories: 5, 5e
Transmission Distance 100 m (between hub and node)
Number of Cascade Connections No restrictions if switching hub is used.
Communication Specifications
CIP Communications: Tag Data Links
Number of Connections 256
Packet Interval (Refresh period) 0.5 to 10,000 ms (Unit: 0.5 ms)
Can be set for each connection. (Data will be refreshed at the set interval, regardless of the number of nodes.)
Permissible Communications Band 6,000 pps (See note 1.)
Number of Tag Sets 256
Type of Tags CIO, DM, EM, HR, and WR
Number of Tags per Connection 8 (Seven tags if PAC status is included in the segment.)
Maximum Link Data Size per Node 184,832 words
Maximum Data Size per Connection 252 or 722 words (See note 2.)
(Data is synchronized within each connection.)
Number of Registrable Tag Set 256 (1 connection = 1 segment)
Maximum Tag Set Size 722 words (One word is used when PAC status is included in the segment.)
Maximum Number of Tags Refreshable in
a Single Cycle of CPU Unit (See note 3.)
Output/send (CPU Unit to EtherNet/IP): 256
Input/receive (EtherNet/IP to CPU Unit): 256
Data Size Refreshable in a Single Cycle
of CPU Unit (See note 3.)
Output/send (CPU to EtherNet/IP): 6,432 words
Input/receive (EtherNet/IP to CPU): 6,432 words
Change of Tag Data Link Parameter
Settings during Operation
OK (See note 4.)
Multi-cast Packet Filter (See note 5.) OK
CIP Communications: Explicit Messages
Class 3 (Number of Connections) Number of connections: 128
UCMM (Non-connection Type) Maximum number of clients that can communicate at the same time: 32
Maximum number of servers that can communicate at the same time: 32
CIP Routing OK (CIP routing is enabled for the following remote Units: CJ1W-EIP21 and CJ2H-CPU6
-EIP.)
FINS Communications
FINS/UDP OK
FINS/TCP 16 connections max.
EtherNet/IP Conformance Test Conforms to A5.
EtherNet/IP Interface 10Base-T/100Base-TX
Auto Negotiation/Fixed Setting
Note 1. “Packets per second” is the number of communications packets that can be processed per second.
2. Large Forward Open (CIP optional specification) must be supported in order for 505 to 1,444 bytes to be used as the data size. Application is supported between CS/CJ-series PLCs.
When connecting to devices from other manufacturers, make sure that the devices support the Large Forward Open specification.
3. If the maximum number is exceeded, refreshing will require more than one CPU Unit cycle.
4. When changing parameters, however, the EtherNet/IP port where the change is made will be restarted. In addition, a timeout will temporarily occur at the other node that was
communicating with that port, and it will then recover automatically.
5. The EtherNet/IP port supports an IGMP client, so unnecessary multicast packets are filtered by using a switching hub that supports IGMP snooping.