User's Manual

7 Modbus/TCP Communications
7 - 54
UHF RFID System V780-series Reader/Writer User’s Manual (Z389)
Function
This command sets the TCP/IP communications conditions of the Reader/Writer.
Command Format
Response Formats
Normal Response
7-6-5 Reader/Writer Setting Commands: Network Settings
SET TCP/IP COMMUNICATIONS CONDITIONS
Byte-0 Byte-1 Byte-2 Byte-3 Byte-4 Byte-5 Byte-6 Byte-7 Byte-8 Byte-9 Byte-10 Byte-11
Transaction identi-
fier
Protocol identifier Field length Unit
identifier
Function
code
Register address Word count
X X 0000 hex 0015 hex FF hex 10 hex B000 hex 0007 hex
Byte-12 Byte-13 Byte-14 Byte-15 ... Byte-18 Byte-19 ... Byte-22 Byte-23 ... Byte-26
Byte
count
TCP/IP communications conditions
0E hex IP address setting
method
IP address Subnet mask Gateway address
2 bytes 4 bytes 4 bytes 4 bytes
Parameter Description Default setting
Register address The register address (B000 hex) that specifies the TCP/IP communications condi-
tions.
Word count The number of words in the TCP/IP communications conditions (0007 hex)
Byte count The number of bytes in the TCP/IP communications conditions (0E hex)
TCP/IP
commu-
nica-
tions
condi-
tions
IP address set-
ting method
Specify in 4-digit hexadecimal the IP address setting method.
0000 hex: Fixed setting
00001 hex: Obtain from BOOTP server
0002 hex: Get from BOOTP server as fixed settings
0000 hex
IP address
*1
*1. Specify 00000000 hex for any IP address setting method other than using a fixed IP address.
Specify in 8-digit hexadecimal the fixed IP addresses to set.
Setting range: 00000000 to DFFFFFFF hex
Example: C0A801C8 hex (192.168.1.200)
C0A801C8 hex
Subnet mask
*1
Specify in 8-digit hexadecimal the subnet mask to set.
Setting range: FF000000 to FFFFFFFF hex
Example: FFFFFF00 hex (255.255.255.0)
FFFFFF00 hex
Gateway
address
*1
Specify in 8-digit hexadecimal the gateway address to set.
Setting range: 00000000 to DFFFFFFF hex
Example: C0A801FE hex (192.168.1.254)
C0A801FE hex
Byte-0 Byte-1 Byte-2 Byte-3 Byte-4 Byte-5 Byte-6 Byte-7 Byte-8 Byte-9 Byte-10 Byte-11
Transaction identi-
fier
Protocol identifier Field length Unit
identifier
Function
code
Register address Word count
X X 0000 hex 0006 hex FF hex 10 hex B000 hex 0007 hex