User's Manual

7 Modbus/TCP Communications
7 - 58
UHF RFID System V780-series Reader/Writer User’s Manual (Z389)
Function
This command is used to set or clear a name for the Reader/Writer.
Command Format
Response Formats
Normal Response
Error Response
SET DEVICE NAME
Byte-0 Byte-1 Byte-2 Byte-3 Byte-4 Byte-5 Byte-6 Byte-7 Byte-8 Byte-9 Byte-10 Byte-11
Transaction identi-
fier
Protocol identifier Field length Unit
identifier
Function
code
Register address Word count
X X 0000 hex 0047 hex FF hex 10 hex B100 hex 0020 hex
Byte-12 Byte-13 ... Byte-76
Byte
count
Device name
40 hex 64 bytes
Parameter Description
Register address The register address (B100 hex) that specifies the device name
Word count The number of words in the device name (0020 hex)
Byte count The number of bytes in the device name (40 hex)
Device name ASCII characters, 64 bytes max.
(63 ASCII characters max. + End code of 00 hex)
If there are fewer than 63 characters, the remaining bytes are filled with 00 hex.
The device name is given with ASCII characters 20 hex (space) to 7E hex (~).
Specify 00 hex for all bytes to clear the device name.
Byte-0 Byte-1 Byte-2 Byte-3 Byte-4 Byte-5 Byte-6 Byte-7 Byte-8 Byte-9 Byte-10 Byte-11
Transaction identi-
fier
Protocol identifier Field length Unit
identifier
Function
code
Register address Word count
X X 0000 hex 0006 hex FF hex 10 hex B100 hex 0020 hex
Parameter Description
Register address The register address from the command is set.
Word count The word count from the command is set.
Byte-0 Byte-1 Byte-2 Byte-3 Byte-4 Byte-5 Byte-6 Byte-7 Byte-8
Transaction identi-
fier
Protocol identifier Field length Unit iden-
tifier
Function
code
Excep-
tion code
X X 0000 hex 0003 hex FF hex 90 hex 1 byte
Parameter Description
Exception code For details, refer to Exception Code on page 7-7 under Response Format for Error
Completion on page 7-7.