Datasheet
NCP1351
http://onsemi.com
15
At this point, the current is fully compressed and remains
frozen. To further decrease the transmitted power, the
frequency does not have other choice than going down.
Figure 16. The NCP1351 Peak Current Compression
Scheme
60 A
80 A
270 A
70 A
40 A
FAULT
(A, B versions)
FB Current
CS Current
Looking to the data-sheet specifications, the maximum
peak current is set to 270 A whereas the compressed
current goes down to 70 A. The NCP1351 can thus be
considered as a multi operating mode circuit:
• Real fixed peak current / variable frequency mode for
FB current below 60 A.
• Then maximum peak current decreases to I
CS,min
over a
narrow linear range of I
FB
(to avoid instability created
by a discrete jump from I
CS,max
to I
CS,min
), between
60 A and 80 A.
• Then if I
FB
keeps on increasing, in a real fixed peak
current/variable frequency mode with reduced peak
current
For biasing purposes and noise immunity improvements,
we recommend to wire a pulldown resistor and a capacitor
in parallel from the FB pin to the controller ground
(Figure 17). Please keep these elements as close as possible
to the circuit. The pulldown resistor increases the
optocoupler current but also plays a role in standby. We
found that a 2.5 k resistor was giving a good tradeoff
between optocoupler operating current (internal pole
position) and standby power.
Figure 17. The Recommended Feedback
Arrangement Around the FB Pin
C1
100nF
V
CC
FB
R1
2.5k
Fault detection
The fault detection circuitry permanently observes the FB
current, as shown on Figure 19. When the feedback current
decreases below 40 A, an external capacitor is charged by
a 11.7 A source. As the voltage rises, a comparator detects
when it reaches 5 V typical. Upon detection, there can be
two different scenarios:
1. A version: the circuit immediately latches-off and
remains latched until the voltage on the current
into the V
CC
pin drops below a few A. The latch
is made via an internal SCR circuit who holds
VCC to around 6 V when fired. As long as the
current flowing through this latch is above a few
A, the circuit remains locked-out. When the user
unplugs the converter, the V
CC
current falls down
and resets the latch.
2. B version: the circuit stops its output pulses and
the auxiliary V
CC
decreases via the controller own
consumption (≈600 A). When it touches the
V
CC(min)
point, the circuit re-starts and attempts to
crank the power supply. If it fails again, an hiccup
mode takes place (Figure 18).
3. C version: this version includes the dual Over
Current Protection (OCP) level. When the
switching frequency imposed by the feedback loop
reaches around 50% of the maximum value set by
the Ct capacitor, the timer starts to count down. If
the fault disappears, the timer is reset. When the
fault is finally confirmed, the controller latches off
as the A version.
4. D version: this version includes the dual Over
Current Protection (OCP) level. When the
switching frequency imposed by the feedback loop
reaches around 50% of the maximum value set by
the Ct capacitor, the timer starts to count down. If
the fault disappears, the timer is reset. When the
fault is finally confirmed, the controller enters
auto-recovery mode, as with the B version.
Figure 18. Hiccup Occurs with the B Version Only,
the A Version Being Latched
V
CC
V
drv
The duty-burst in fault is around 7% in this particular
case.