3. PRODUCT SPECIFICATIONS
Model Name OD330 OD330-AL OD500 OD1000
Capacity 330 VA / 200 W 500VA/300W 1000VA/600W
Voltage 120V/220 Vac ± 30 %
Input
Frequency 50/60 Hz ± 10 %
auto sensing
Voltage
(on battery mode)
Square wave 220 Vac ± 5 %
Frequency
(on battery mode)
50/60 Hz ± 1 Hz
Automatic voltage
adjustment
When the input voltage is 9 % to 15 % lower than the utility, the UPS
automatically boosts the voltage by 15 %
When the input voltage is 9 % to 15 % higher than the utility, the UPS
automatically bucks the voltage by 13 %
Output
Transfer Time 4ms (typical)
Surge protection 250 J2 m s
Overload protection
When the load is more than 110%, the UPS will automatically
shut down in 60 seconds
When the load is more than 130%, the UPS will automatically
shut down in 3 seconds
EMIRFI filter 10 db at 0.15 MHz, 50 db at 30 MHz
Short circuit Immediately cut off the input or output circuit breaker protection
Battery low voltage Low voltage discharge protection, battery failure warning
Too hot Automatically turn on the cooling fan
Protection &
Filtering
Higher or lower voltage Switch to battery mode
Quantity
1 * 12V batter
2 * 12V batteries
parallel connection
2 * 12V batteries
Series connection
Charging current 5A/10A/15A/20A
Battery
Battery protection Discharge low voltage protection, battery failure warning
Mains electricity normal Green light is on
Battery mode Orange light is on
Indicators
Battery / UPS fault Red light is on
Working environment -2060, highest 3500m, 095% (without condensation
Working noise < 40db1 meter away from the UPS surface
Environment
Storage 0 to 15000m
Weightkg
(excluding the battery)
Net weight 16
Gross weight 18
Net weight 23
Gross weight 25
Net weight 25
Gross weight 28
Dimensions W×D×H
including installation
support and handle
535×310×580
mm
535×310×870mm
Physical
Connections Wirable terminal blocks
6
4. Installation
4.1 Inspection
Please inspect UPS immediately for missing parts or other problems.
Should there be any damage, please notify the seller.
4.2 Installing the UPS Cabinet
z Electric pole installation: Anchor Ear Installation. Behind the UPS
cabinet are 2 installation poles. Please pick the size of the installation
poles that you will need.
z H-pole installation: Fastening Screw Installation. Below the UPS
cabinet are 2 installation poles. The UPS is placed on the H-pole, and
four fastening screws are used to fix the UPS cabinet.
z Wall installation: Expanding Screws plus A-Frame Installation. The
expanding screws are fixed on the wall according to the distance of
four installation holes. Then the A-frame will be installed and
fastened on the 2 installation poles below the UPS cabinet.