User Guide Durable Series Models DS1000B, 1500B, 2000B, 3000B DS1000B-RM, 1500B-RM, 2000B-RM, 3000B-RM
LIMITED WARRANTY For your records The serial number of your UPS is on the rear panel. You should note the serial number in the space provided below. Retain this booklet as a permanent record of your purchase to aid in identification in the event of theft or loss. What the warranty covers: We warrant this product to be free from defects in material and workmanship during the warranty period.
Opti Australia reserves the right to request proof of purchase upon any warranty claim. Limitation of implied warranties: Life Support: THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, WHICH EXTEND BEYOND THE DESCRIPTION CONTAINED HEREIN INCLUDING THE IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
TABLE OF CONTENTS EMC Statements 1. Introduction ...........................................................................................3 2. System description...............................................................................
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS ● CAUTION (UPS Having Internal Batteries): Risk of electric shock – Hazardous live parts inside this unit are energized from the battery supply even when the input AC power is disconnected. ● CAUTION (No User serviceable Parts): Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
1. Introduction z DC power is converted to AC in the inverter passing it on to the load. The information provided in this manual covers single phase 1000 – 3000 VA, uninterruptible power systems, their basic functions, operating procedures, and emergency situations, also including information on how to ship, store, handle and install the equipment. Only detailed requirements of the UPS units are described herein, and installation must be carried out in accordance with this manual.
sends any forewarnings if replacement is needed. Otherwise every 30 days of normal mode operation, a battery discharge test is performed and any problems reported on the LCD display. Except during the first 24 hours after startup while the UPS is in charging mode (please see chapter 7.2), diagnostic tests can be performed manually from the front panel at any time. 2.2 System Configuration The UPS device and the internal backup battery make up the system.
4. Storage Installations with accessories of “Vertical” and “Wall-mounted” types: Please adhere to the following instructions if the UPS is not installed immediately: Please install the vertical and wall-mounted types of units according to the following illustration. z Store the equipment as is in its original packing and shipping carton z Do not store in temperatures outside the range of +15°C to +25°C. z Ensure that the equipment is fully protected from wet or damp areas and from moist air.
Installation with accessories of “Rack-mounted” types: Please install the types of units according to the following illustration. 5.2 Rear panel views 1KVA - 1.5KVA Rear Panel SMART SLOT (OPTIONAL) Note: The product diagrams below are used for illustrating installation procedure only. They may not be exactly the same with the product you purchased. Installation with bottom bracket.
2KVA-3KVA Rear Panel RM (1U) 1KVA Rear Panel SMART SLOT (OPTIONAL) EPO RS232 CIRCUIT BREAKER DATA LINE PROTECTION USB EPO RS232 SMART SLOT (OPTIONAL) BATTERY BACKUP OUTLETS EXTENDED BATTERY CONNECTOR INPUT USB (100/110/120V) CIRCUIT BREAKER CIRCUIT BREAKER EPO RS232 SMART SLOT BATTERY BACKUP OUTLETS INPUT USB (220/230/240V) CIRCUIT BREAKER BATTERY BACKUP OUTLETS INPUT RM (2U) 1KVA – 1.
RM (2U) 2K-3KVA Rear Panel BATTERY BACKUP OUTLETS 5.
6. Computer and Alarm connections At the back of the UPS is an interface allowing direct communication with your computer system, the location of which can be found in figure 2. There is a RS232 serial data interface, one USB data interface and an emergency power off switch supplied. However, the RS232 port cannot be used when the USB interface is in use. In addition there is an optional interface slot that allows you to install different communications cards.
USB port 7. User’s guide to operations Connecting the UPS to your computer is accomplished through the USB port on the back of your computer. USB compliant hardware and operating system will be necessary including installation of a UPS driver. The serial port cannot be used when using the USB port. Necessary information for operation of the unit is covered in this chapter.
(b) If no button is pressed within 10 seconds, it will return to original status. Status of the UPS, measurements and alarms are all indicated on the LCD screen. 3. “FUNC” is a Function button. Each function can be enabled by pressing this button. (a). Push the “FUNC” button (at least 2 seconds) to choose which function that you want. Each content can be displayed by pressing at once, and it has fourteen kinds of function to be checked. (b).
UPS configurations 1. Various settings that have been chosen are shown in the UPS setting display. 2. To enter configuration mode, press the “FUNC” button for one second. The first configuration parameter will be shown on the LCD display. Settings LCD display Explanation Output Volt. Setting O/P V Setting Select Nominal Voltage 3. Press the “FUNC” button to scroll through the parameters.
Manual test of the UPS 7.5 Trouble shooting Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well and are functional even when the UPS is not charging the battery. Displayed on LCD Output Overload Manual Battery test: Scroll the parameters until Manual Bat test displays on the LCD. Press the “Enter” button twice.
8. Maintenance With a minimal amount of maintenance, you can expect the UPS to function normally. However, the batteries may need to be changed every 2 – 3 years as it reaches the end of its service life. The most critical issues for the reliability of the UPS are environmental issues. Ensure that the temperature and humidity are always according to specifications and keep the area around the unit clean and dust free. At a constant temperature of 25°C, the typical battery lifetime is about 4 years.
9. Warranty Warranty on this product is valid against defects in material and workmanship for a period of 24 months from its original date of purchase. 10. Technical Specifications 120/140/160 VAC-276 VAC 50/60 Hz. Auto selection 45-65 Hz ± 3Hz. 1000 VA 4A, 1500 VA 6A, 2000 VA 7.7A, 3000 VA 12A Input Power factor: 0.97 OUTPUT 10.1 Power Range 1000-3000 VA (100/110/120V) GENERAL Rated power Technology 1000 VA, 1500VA, 2000 VA, 3000 VA at p.f 0.
Frequency regulation ± 0.25 Hz (battery or free running mode) * 60V at 40% load, 70V at 70%, 80V at 100%. ENVIRONMENTAL Ambient temperature: +0 °C to +40 °C Recommended temperature: +15 °C to +25 °C Storage temperature: -15 °C to +50 °C Cooling: Forced air-cooling Humidity: 0-95%, non-condensing Audible noise: < 40 db normal and battery mode 10.4 Power Range 1000-3000 VA (220/230/240V 19” Rack-mount model) GENERAL Rated power Technology 1000 VA, 1500VA, 2000 VA, 3000 VA at p.f 0.
10.5 Battery Packs 220/230/240V Model OUTPUT POWER Connection Input 1000VA/700W 1500VA/1050W IEC 320 (10A) IEC 320 (10A) 2000VA/1400W 3000VA/2100W IEC 320 (10A) IEC 320 (16A) 8 x IEC 320 (10A) 8 x IEC 320 (10A) Connection Output 4 x IEC 320 (10A) 4 x IEC 320 (10A) 1 x IEC 320 (16A) 1 x IEC 320 (16A) Lead-acid Lead-acid Lead-acid Lead-acid Battery type 7.2Ah/12V 9Ah/12V 7.