User Manual

Page 4/4 Operating instructions for DALI CON 1 – 10V SO Operating instructions for DALI CON 1 – 10V SO Page 1/4
Wiring diagram: DALI CON 1 – 10V SO in DALI mode (operation as converter)
12345 6 7
109
8
NL
TDADA
+-
1...10V
0...10V
DA
DA
L
N
PE
F1
10A
max
1...10V
/
0...10V Geräte:
EVGs, Dimmer,
elektr. Trafos usw.
Kontaktbelastbarkeit
beachten !
weitere DALI-Geräte
1...10V
/
0...10V
PE
N
-
+
DALI
Converter 1 - 10V
DALI CON 1 - 10V SO
Wiring diagram: DALI CON 1 – 10V SO in 1-button mode (Converter as light control unit)
12345 6 7
109
8
NL
TDADA
+-
1...10V
0...10V
S1
L
N
PE
F1
10A
max
PE
N
-
+
1...10V/0...10V Geräte:
EVGs, Dimmer,
elektr. Trafos usw.
Kontaktbelastbarkeit
beachten !
1...10V/0...10V
Converter 1 - 10V
DALI CON 1 - 10V SO
Subject to change without notice. Errors and omission excepted 02.03.2011 V1.2.
Operating instructions DALI CON 1 – 10V SO Converter from DALI to 1-10V
Applications and functions
DALI converter CON 1 – 10V SO is a multifunctional unit. On the one hand it is a converter (see DALI
mode) which is accessed digitally via the DALI interface in the same way as a DALI ECG, and on the
other hand it is a lighting controller in its own right (see 1-button mode). With its control output
(combined interface 1-10V/0-10V) and load contact, ECG and electronic transformers can be dimmed
and switched via 1-10V and dimmers via 0-10V.
The characteristic for the control voltage at the output can be set to logarithmic 1-10V (for ECG and electronic
transformers) or to linear 0-10V (for power dimmers) depending on the application. CON 1 – 10V SO is
enclosed in an insulated casing in snap-on design for standard distributor installation. A unit with the identical
function in a metal casing for installation in luminaires is also available in (DALI CON 1 – 10V LI).
It is therefore possible to connect DALI with existing 1-10V/0-10V systems, combine the two systems or even
set up separate lighting control systems.
1-10V / linear characteristic 0-10V/ logarithmic characteristic
DALI mode (operation as converter)
The converter communicates via the DALI interface with the controller (e.g. OSRAM Room Controller DALI RC
BASIC SO). It receives DALI commands from there and also the interface supply voltage. DALI signals are
converted to 1-10V/0-10V signals, including on/off switching via the load contact. The DALI lines (DA/DA) are
connected to the controller for this purpose. The converter is accessed and addressed by the controller in the
same way as a DALI ECG. All the 1-10V/0-10V units connected to the converter are considered as a uniform
group under the address assigned to the converter. Detection of lamp faults and "physical selection"
(deactivation and reactivation of the lamps during system startup) are not supported in the 1-10V/0-10V
system.
!In DALI mode, the additional switch input (T) may not be connected!
Behaviour on return of mains voltage in DALI mode (ex factory setting):
Without the controller the load contact is closed and output voltage goes to 10 V (100%). If a controller is
connected, the behaviour is determined by the controller (see controller description).
1-button mode (operation as controller)
In this mode the converter operates as an independent lighting controller with a 1-button switching/dimming
function independently of DALI. It is operated by a switch (make contact/230Vac) which switches from input T
to phase L. To access this mode a long press is needed (enabling the 1-button mode). The converter remains
in this mode until it is reset to DALI mode on receipt of a DALI command via the DALI interface.
!In 1-button mode, the DALI interface may not be connected!
Mode I:
Short press: Switch On/Off, long press: Switch On-brighter/brighter/darker.
The switch on light level is equal to the last level before switch off (automatic memory function).
Mode II:
Short press: Switch On/Off, long press: Switch On-brighter/brighter/darker.
The switch on light level is stored by a double click (= 2 x short press) in switched on state. The storage is
signalised by flashing of the lighting.
Change to mode I: Switch off the light by a short press and make a double click to the push button
afterwards. The converter switches on with 100% light and is now in mode I.
Change to mode II: Make a double click when the light is switched on. The light flashes and the current light
level is stored as switch on level. The converter changes to mode II respectively stays in mode II.
Behaviour on return of mains voltage in 1-button mode:
Switching state and dimming level are restored automatically
Other DALI units
1-10V/0-10V units
ECGs, dimmers,
electr. Trans-
formers, etc.
Check contact rating!
1-10V/0-10V units
ECGs, dimmers,
electr. Trans-
formers, etc.
Check contact rating!

Summary of content (2 pages)