User Manual

Page 2/4 Operating instructions for DALI CON 1 – 10V SO Operating instructions for DALI CON 1 – 10V SO Page 3/4
Converter 1 - 10V
Typ:
CON 1 - 10V SO
Lastkontakt
max. 5A~
DA
-
+
7
DA
8
out
1...10V
0...10V
910
L
L
NTN
230V~ 50/60Hz
Nur für Wechselspannung!
3456
1
2
L`
in
µ
DALI interface
Interface in accordance with the DALI definition. Current input <2mA DC. Electrical isolation via opto-coupler
from mains and output: basic insulation (no safety extra-low voltage).
The converter does not have an integrated power supply for the DALI interface. The power supply for the DALI
interface has to be part of the DALI controller.
Output (combined interface) 1-10V/0-10V
Interface for controlling 1-10V units (max. -100 mA current sink e.g. for ECGs, electronic transformers, etc.)
and/or 0-10V units (max. +3 mA active e.g. for power dimmers, etc.). Electrical isolation from the mains and
DALI: basic insulation (no safety extra-low voltage).
Characteristic switch
Switching option for the characteristic for the control voltage at the output. Linear from 0 – 10V, usually for
power dimmers. Logarithmic from 1 – 10V, usually for ECGs and electronic transformers.
Load contact
Internal relay (make contact) not floating. The load contact is connected internally with L. Suitable for direct
on/off switching of small systems. Check the contact load rating. Add an external relay or contactor for larger
systems. On/off switching as function switching.
Switch input
Switch input for operating in 1-button mode. Switching takes place to L (make contact/230Vac). Internal opto-
coupler to N (mains potential).
Electrical isolation from the output and DALI: basic insulation (no safety extra-low voltage).
Safety and installation instructions
Power to the units must be switched off before any work is undertaken.
The units should be installed and tested only by a qualified electrician.
Wire the terminals as shown in the wiring diagram. Follow the wiring diagrams and any
instructions printed on the unit.
The relevant safety and accident prevention regulations must be observed.
The relevant installation instructions must be observed.
The unit must not be opened or operated without its casing.
Usage of DALI and 1-button operation at the same time is not allowed!
The converter may be damaged or destroyed if wired incorrect.!
Technical data
Designation: Converter from DALI to 1-10V
Type: DALI CON 1 – 10V SO
Mains voltage: 230Vac 50/60 Hz, DC not permitted
Power consumption: approx. 1 W
Fuse protection: External max. 10 A, (load contact is connected internally to L)
Operating temperature: 0°C to 45°C
Protection class/type of protection: II(insulated)/IP20
Pollution severity: 2 (dry not conductive)
Load contact L` (µ): Relay contact internal (make contact), connected internally with L
Function switching (on/off), no reliable isolation (µ contact gap)
Load capacity L` (µ): max. 10 A~ ohmic load
max. 5A~ ECG load:
30 St.
EVG HF 1x 18W or 1x36W or
20 St.
EVG HF 2x18W or 2x36W or
15 St. QTi DIM 1x14/24 or 1x18 or 1x21/39 or 1x28/54 or 1x36 or 1x58 or
15 St. QTi DIM 3x18 or
10 St. QTi DIM 1x35/49/80 or 2x14/24 or 2x18 or 3x14/24 or 4x18 or
8 St. QTi DIM 2x21/39 or 2x28/54 or 2x35/49 or 2x36 or 2x58 or 4x14/24 or
5 St. QTi DIM 2x35/49/80
Output out: 1-10V max. -100mA DC, current sink (approx. 100 ECG or electronic
transformers– see manufacturers' data–)
Control voltage: 0-10V max. +3mA DC (power dimmers –see manufacturers' data–)
Dimming curve: Switchable between: linear 0-10V and logarithmic 1-10V characteristic
DALI interface: Acc. DALI standard, current input <2mA DC, interface non-polarised
Switch input (T): Switch (make contact) for mains voltage (230Vac)
Terminals: Plug-in terminals, single-wire or fine wire: 0.3 - 2.5 mm
2
Mains: L, N Terminal no. (2/3, 4/5)2 and 3, 4 and 5 internally
connected
Load contact: L` (µ) Terminal no. (1) internal connected to L
DALI interface: DA, DA Terminal no. (7, 8) non-polarised
Switch input: T Terminal no. (6)
Output out: 0-10V 1-10V DC +, - Terminal no. (9, 10) polarised
Maximum cable lengths : DALI wire Î see data sheet of the corresponding controller
Push button and 0-10V/1-10V input Î 100m
Cable routes: The relevant wiring requirements governing cable routes, insulation,
fusing and minimum cross-sections must be observed.
Housing: isolated casing for cabinet / DIN rail installation
Dimensions: WxHxD=72 x 90 x 64 mm, see dimensional drawing
Weight: approx. 220g
Labelling: CE
Terminal assignment: See wiring diagrams and information printed on unit