Electronic Transformer with DALI
®
interface for 12 V halogen lamps
Features
Dimmable via DALI
®
interface
(according to DALI
®
standard) or
TouchDIM
®
or TouchDIM
®
Sensor
Suitable for emergency installation
Reversible switch off in case of short-
circuits, overload and overtemperature
Compliance with all relevant standards
Connecting the transformer
to the lamps
Ensure that the lamp load is within the
output range of the transformer (see
table)
Transformer can be connected in
parallel on the primary side (see
fig. 1a)
Do not connect the transformer in
parallel or series on the secondary
side (see fig. 1b)
Wiring
In accordance with EN 60598 standard,
the recommended connecting cables
(see table) must be held firmly by the
cable clamp to prevent it from being
pushed or pulled
Secondary side: cable length maximum
2 m, minimum 0.3 m (fig. 2)
To prevent radio interference keep lamp
cables as short as possible, keep them
away from metal surfaces and keep
them separated as far as possible from
mains cables (fig. 2: angles 90°). Do
not route cables along the transformer
When using single leads of a cable,
secondary wires have to be twisted in
pairs
For units installed in fixtures the
luminaire manufacturer is responsible
for RFI-compliance
Temperatures
Avoid high temperatures. Do not place
the transformer close to the lamp
(minimum distance 0.3 m). Maximum
ambient temperature must not exceed
50 °C. Make sure there is adequate
space to avoid a build-up of heat. In
critical installations the temperature at
t
c
has to be controlled.
Caution
Transformers must be installed by
a qualified electrician
Electronic transformers are not suitable
for any other load than low voltage
halogen lamps
No switching or dimming on the
secondary side
General hints
Do not use DALI
®
control and
TouchDIM
®
or TouchDIM
®
Sensor
simultaneously (see fig. 4 and 5)
In case of emergency installation it is
recommended to short-circuit the
DALI
®
interface (e.g. with a relais) while
emergency operation.
For further information please refer to
“HALOTRONIC – Technical guide” or
“DALI-Technical Guide” available at:
www.osram.com/ecg-downloads
HALOTRONIC
®
INTELLIGENT DALI
®
1. a
2.
1. b
3. Wire stripping
correct incorrect
35 W
35 W
35 W
100 W
HTi DALI
105
HTi DALI
105
HTi DALI
105
35 W
90°
Optimum
area for
primary cables
Optimum
area for
secondary
cables
Prim. Sec.
HTi DALI
105
max. 2 m
min. 0.3 m
90°
mains
next
unit
not used
16 mm
7 mm
10 W
120 W
HTi DALI
105
HTi DALI
105
HTi DALI
105
HTi DALI
105
HALOTRONIC
®
INTELLIGENT DALI
®

Summary of content (2 pages)