Owner's manual

1
Application hints for
OSRAM Touch DIM function
With Touch Dim, OSRAM DALI ECG can be used as convenient dimmers with a memory function by connection of a normal
push button. Touch Dim is no part of the DALI standard but an additional function offered by OSRAM DALI control gears:
- Electronic Control Gear for fluorescent lamps: QTi DALI … DIM
- Low voltage halogen transformer: HTi DALI 150/220-240 DIM
- LED dimmer: OTi DALI DIM
Important !!!
DALI and Touch DIM must never be used at the same time! In other words, control is achieved either with DALI controller or
with the Touch DIM function.
Wiring instructions and compensation:
Fig.: Up to 4 ECGs can be controlled via Push Button Usage. The number of Push Buttons is limited by the sum of the
overall cable length between switch(es) and the connected ECGs which may not exceed 25m.
Switches with glow lamp must not be used. For a cable length of more than 25 m, compensation must be provided for the line
capacitance by connecting a transformer with the following features: primary side 230 V / secondary side 12 V, required power
of transformer: 25 mW per connected ECG (e.g. 100 mW for 4 ECG, 250 mW for 10 ECG a.s.o.) .
either: or:
Option A
: Transformer located close to the ECG Option B: Transformer located close to the push
(e.g. inside the luminaire) button (e.g. inside a recessed flush-device box)
ENGLISH
12 V transformer
min. power: 25 mW x number of ECG
DA
DA
~
~
Push
button
L
N
PE
DALI ECG
Installation cable
DA
DA
~
~
Push
button
L
N
PE
Installation cable
DALI ECG
12 V transformer
min. power: 25 mW x number of ECG