User's Manual

Performing Advanced Functions
Short
Battery (5,6 to 10V)
1
2
3
4
5
+
-
Fig. 11: A73x Connection with External Battery
If you want to use the internal battery with a different power supply (charger) than
the provided solar panel, disconnect the solar panel and use the configuration
shown in Fig. 12.
Short
Charger (9 to 10V,
100 to 300mA)
1
2
3
4
5
+
-
Fig. 12: A73x Connection with External Power Supply
And if you want to use an external battery with a different power supply (charger)
than the provided solar panel, disconnect the internal battery and solar panel and
use the configuration shown in Fig. 13.
Short
Charger (must
fit the battery)
1
2
3
4
5
+ +
Battery
(5,6 to 10V)
Fig. 13: A73x Connection with External Battery and Power Supply
3.2 Communicating with the RTU
You can use a Windows HyperTerminal window to connect to the A73x RTU. After
you have installed the system, follow these steps to configure the device and set
the default parameters:
Note: To configure the A73x RTU, you must have a special adapter cable (available from
Adcon) and plug it into the POWER connector.
1. Start a HyperTerminal session.
2. Select the appropriate serial port and click OK.
3. Configure your terminal as follows:
19200 baud
1 stop bit - 8 data bits
No parity
No protocol (neither hardware nor software)
4. Select OK to open the terminal window.
5. Press Enter to generate a response in the window.
21