User's Manual

Performing Advanced Functions
SLOT
CAUTION Changing these parameters may adversely affect the ability of the device to
operate for extended periods under low solar radiation conditions.
A
VAILABLE FOR
A731 A733A732 A733GSM
D
ESCRIPTION Sets/returns the node’s sampling interval and rate.
PARAMETERS The interval (60 - 65535) and rate (0 - 255). The interval represents the time (in
seconds) elapsed between two slots stored in the internal memory, while the rate
represents the numbers of samples used to build the average that will be stored.
RETURNS The interval and rate.
REMARKS GET/SET. The default interval is 900 (15 minutes) and rate is 15 (15 samples per
quarter of an hour).
REMOTE Yes, SET only.
E
XAMPLE SLOT 900 15
9193 SLOT 0
#
SLOT
9193 SLOT 900 15 0
#
SST
AVAILABLE FOR
A731 A733A732 A733GSM
DESCRIPTION Sets/returns the RTUs sensors settling time; this is the time that elapses between
powering the sensors and sampling them. Default value is 2 seconds.
PARAMETERS The settling time in seconds.
RETURNS The current settling time.
REMARKS GET/SET.
REMOTE Yes, SET only.
EXAMPLE SST 3
9193 SST 0
#
SST
9193 SST 3 0
#
PMP
AVAILABLE FOR
A731 A733A732 A733GSM
DESCRIPTION Sets/returns the node’s Power Management Parameters (switches on/off the
battery charge).
P
ARAMETERS The lower (switch on) and the higher limit (switch off), both in volts x 10. Standard
Values are 65 (for 6.5 Volts) for switch on and 72 (for 7.2 Volts) for switch off (for a
standard 6.2 Volt NiCd battery). From these values, other thresholds are internally
computed.
R
ETURNS The lower (switch on) and the higher limit (switch off), both in volts x 10.
R
EMARKS GET/SET.
25