User's Manual

Performing Advanced Functions
SDI value (floating point).
(see also the example below)
For additional information on the significance of the SDI address, method and
index, please see also the SDI-12 standard specification (http:// www.sdi-12.org).
The digibyte is similar to the DATA command:
SC Dig6 Dig5 Dig4 Dig3 Dig2 Dig1 Dig0
b7 b0
SC-Battery Charge (0-off, 1-on) Dig n – Digital I/O n
Fig. 19: The Digibyte
The remote version is limited to a single frame.
REMARKS GET only.
R
EMOTE Yes.
E
XAMPLE 12800 datasdi
12800 datasdi 16 5 2003 20 14 49 44 60 255 255 127 87 9 0 9 3
0 0 74.379401 3 0 1 68.117003 3 0 2 58.832397 3 0 3 51.611795
3 0 4 38.346400 3 0 5 19.800799 3 0 6 14.895999 3 0 7
3.553500 3 0 8 0.037200 2953 0
#
SDA
AVAILABLE FOR
A731 A733A732 A733GSM
DESCRIPTION Sets/returns the maximum delay for waiting awake (i.e. out of sleep mode) for a
service request of an SDI-12 sensor. This parameter is set to 30 seconds by
default. A larger value may lead to higher power consumption. This should be used
in cases an SDI-12 sensor needs large time values to return a sensor result. If you
have such sensors and still want to use them, you need to change this parameter,
but please be aware of the fact that the RTU’s power consumption will be higher.
PARAMETERS Maximum wake time in seconds (1 to 999).
R
ETURNS The current value (in seconds).
REMARKS SET/GET.
REMOTE No.
E
XAMPLE SDA
29000 SDA 30 0
#
SDA 50
29000 SDA 0
#
FPC
AVAILABLE FOR
A731 A733A732 A733GSM
DESCRIPTION: This command allows the use of sensors which generate pulses with frequencies
from 0.5Hz up to 30Hz.
41