User's Manual

CHAPTER3
UsingTerminalCommands
27
discharge). To compute the actual value (in °C), the following
equation must be used:
Temp
C
internalTemp 400
255
-------------------------------------------------
68=
days_uptime in days; with hr:min_uptime, it represents the
amount of time the device is up without a reset or watchdog.
hr:min_uptime in
hours:minutes format.
rssi as deci
mal; it is the programmed value with the RSSI
command.
pmp_low and pmp_high are the programmed values with the PMP
command.
type is used to rep
resent the device type. The following types are
assigned currently:
— 0 for A730MD
— 1 for A720
— 2 for A730SD
— 3 for A720B
— 4 for A733
— 5 for A723
— 6 for A440
— 7 for A733 GSM
— 8 for A731
— 9 for A732
— 10 for A740
— 11 for A740 GSM
— 12 for A724
— 15 for A723_Series 4
— 16 for A724_Series 4
— 21 for A753GSM
slot and samples are the actual v
alues programmed by means of
the SLOT command.
po is the relative output power of the device.
err_
level is the error value; 0 means no error.
REMOTE Yes, GET only.
EXAMPLE # 42914 info
42914 info 0 31 01/01/1970 00:00:00 1.2 0 0 0 83 60 0 00:40
0 65 7
2 24 900 0 0 0
#
PMP
D
ESCRIPTION Sets/returns the node’s Power Management Parameters (switches the
battery charge on/off).
PARAMETERS The lower (switch on) and the higher limit (switch off), both in volts x
10. Standard Values are 65 (for 6.5 volts) for switch on and 72 (for