OutBack Power FLEXMax Series Owner's Manual
MATE3 Screens
900-0009-01-00 Rev C 67
Night Light
Figure 70 Night Light
Float
Figure 71 Float
Diversion: Relay and Solid St
Figure 72 Diversion:Relay and Diversion: Solid St
Low Batt Disconnect
Figure 73 Low Batt Disconnect
Remote
Figure 74 Remote
Restart Mode
This item selects between continuous MPPT, or occasional MPPT restarts. (See pages 21 and 52.)
Figure 75 Restart Mode
Set Points:
0
– Continuous MPPT,
1
– Automatic re-sweep every 90 minutes
in MPPT charging,
2
– Automatic re-sweep every 90 minutes in
any mode.
Set Points: None
This mode can also be used for the MATE3’s AGS function. See
pages 41 and 66 for important information on this function.
Set Points :
None
Set Points:
Disconnect
Re-Connect
Disconnect Dela
y
Set Points (NOTE: All items function identically for both Diversion:
Relay and Diversion: Solid St, except for
Active: High
or
Low
):
Active: High
or
Low
. (Not present in
Diversion: Solid St
)
Relative Voltage
Hysteresis
Hold
Delay
Set Points :
Active: High
or
Low
.
Threshold
Hysteresis Time
ON Time