Outback Power FLEXPower Radian Series Quick Start Guide

CAUTION: Equipment Damage
These procedures should be done by a qualified installer who is trained on programming inverter power systems.
Failure to set accurate parameters for the system could potentially cause equipment damage. Damage caused by
inaccurate programming is not covered by the limited warranty for the system.
IMPORTANT
Check the firmware revision of all OutBack devices before use. The Radian inverter and MATE3 system display may not
communicate or operate correctly unless their firmware is above a specified revision number.
For models GS8048A and GS4048A, the firmware must be revision 001.005.xxx or higher.
The MATE3 must be revision 002.017.xxx or higher.
Quick Start Guide
900-0176-01-00 REV A.vsd\Page-1\2015-04-29
©2015 OutBack Power Technologies. All Rights Reserved.
Setup and Programming
Contact Technical Support:
Telephone: +1.360.618.4363
Email: Support@outbackpower.com
Website: www.outbackpower.com
FP-Radian
WARNING: Fire/Explosion Hazard
Do not place combustible or flammable materials within 12 feet (3.7 m) of
the equipment. This unit employs mechanical relays and is not ignition-
protected. Fumes or spills from flammable materials could be ignited by sparks.
WARNING: Personal Injury
Use safe lifting techniques and standard safety equipment when working with
this equipment.
IMPORTANT:
Clearance and access requirements may vary by location. Maintaining a 36”
(91.4 cm) clear space in front of the system for access is recommended.
Consult local electric code to confirm clearance and access requirements
for the specific location.
IMPORTANT:
Not intended for use with
life support equipment.
Note: See the MATE3
manual for details on
generator control.
The MATE3 Configuration
Wizard allows quick setup of
parameters that apply to all
systems. The Configuration
Wizard is reached from the
MATE3 Main Menu as shown
to the right.
The firmware revision of all
devices can be confirmed by
navigating from the MATE3
Main Menu as shown below.
Upgrades to the firmware
revision can be downloaded
from the OutBack website
www.outbackpower.com.
S
Firmware Revision
Configuration Wizard
Off Grid
Grid Tied Backup
This advances the display to the
Setup Complete screen.
C
C
C
S S S
C
This advances the display to the
Setup Complete screen if the
FLEXnet DC is not installed. If the
FLEXnet DC is installed, the display
advances to the Shunt screens.
For FN-DC ... For FN-DC ... For FN-DC ...
Generator Installed Y
Generator Type AC Size 5.0 kW
Generator Start Manual
AUX Output Device Port 1
Back Continue
New Configuration >>
Existing Configuration >>
Restore Configuration >>
System Type Grid Tied
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity 500 Ah
Back Continue
Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC
Back Continue
New Configuration Initialized
Back Continue
Shunt A
Connection Inverter
Back Continue
Shunt B
Connection Charge Controller
Back Continue
Shunt C
Connection Charge Controller
Back Continue
Period 1 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00
Back Continue
Period 2 Enable N
Weekday Use 0:00 Drop 0:00
Back Continue
Period 3 Enable N
Weekday Use 0:00 Drop 0:00
Back Continue
Shunt A
Connection Inverter
Back Continue
Shunt B
Connection Charge Controller
Back Continue
Shunt C
Connection Charge Controller
Back Continue
Mode Disabled
Grid Connect 48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%
Back Continue
Shunt B
Connection Charge Controller
Back Continue
Shunt C
Connection Charge Controller
Back Continue
Period 3 Enable N
Weekday Use 0:00 Drop 0:00
Back Continue
Mode Disabled
Grid Connect 48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%
Back Continue
Period 1 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00
Back Continue
Generator Installed N
Generator Type AC Size 5.0 kW
Generator Start Manual
AUX Output Device Port 1
Back Continue
AC Output Voltage 240 VAC
AC Phase Single
AC Input Breaker Size 50 A
Maximum Output Load 33 A
Back Continue
Period 2 Enable N
Weekday Use 0:00 Drop 0:00
Back Continue
Generator Installed N
Generator Type AC Size 5.0 kW
Generator Start Manual
AUX Output Device Port 1
Back Continue
Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC
Back Continue
AC Output Voltage 240 VAC
AC Phase Single
AC Input Breaker Size 50 A
Maximum Output Load 33 A
Back Continue
System Type Backup
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity 500 Ah
Back Continue
Shunt A
Connection Inverter
Back Continue
AC Output Voltage 240 VAC
AC Phase Single
AC Input Breaker Size 50 A
Maximum Output Load 33 A
Back Continue
Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC
Back Continue
System Type Off Grid
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity 500 Ah
Back Continue
Settings >>
Configuration Wizard >>
Device Data Logs >>
Event Logs >>
Firmware Update >>
System >>
Inverter >>
Charge Controller >>
Battery Monitor >>
MATE3 >>
System
System Information >>
Save / Store Information >>
Firmware Version >>
Date and Time >>
LCD Display >>
MATE3 002.017.018
1: GS8048A 001.005.002
2: GS8048A 001.005.002
Settings >>
Configuration Wizard >>
Device Data Logs >>
Event Logs >>
Firmware Update >>
Settings
Configuration Wizard
New Configuration
!
Masters of the Off-Grid.™
First Choice for the New Grid.
In 23.2 V 0.0 A
Out 27.6 V 0.0 A
0.000 kW 0.0 kWH
AUX: OFF Sleeping
In 23.2 V 0.0 A
Out 27.6 V 0.0 A
0.000 kW 0.0 kWH
AUX: OFF Sleeping
Inverter/Charger
GS Load Center
GS8048A
FPR-8048A
Components Included
GSLC175-PV-120/240
Charge
Controller
FM80-150VDC
(x 2)
MATE3
(with FW-MB3-S
mounting bracket)
All Models
System Display
and Controller
Communications
Manager
HUB10.3
Wall Mount Bracket
Pre-wired Back Plane
Inverter/Charger
GS Load Center
GS4048A
FPR-4048A
GSLC175-PV1-120/240
Charge
Controller
FM80-150VDC
(x 1)
Battery Monitor FLEXnet DC (FN-DC)
Remote Temperature Sensor (RTS)
AC Source
Utility Grid or
AC Generator
Main Electrical Panel (or overcurrent
device for the AC source)
Electrical Distribution Subpanel
(Load Panel)
Photovoltaic (PV) Array and Combiner
Customer-Supplied Components
Battery Bank