Radian Series Specications 02/2014
Models:
Domestic (For Selected North, Central and Latin American Countries) International (For Europe, Asia and other Global Countries)
GS8048A GS4048A GS7048E GS3548E
Nominal DC Input Voltage
48VDC 48VDC 48VDC 48VDC
Continuous Output Power (@ 25°C)
8000VA 4000VA 7000VA 3500VA
AC Output Voltage (Selectable)
120/240VAC 120/240VAC (200-260VAC) 230VAC (210-250VAC) 230VAC (210-250VAC)
AC Output Frequency (Selectable)
60Hz (50Hz) 60Hz (50Hz) 50 (60Hz) 50Hz (60Hz)
Continuous AC Output Current (@ 25°C)
33.3AAC @ 240VAC 16.7AAC 30AAC 15.2AAC
Idle Consumption (Invert Mode, No Load)
34W 34W 34W 34W
Typical Eciency
92.5% 92.5% 92% 92%
CEC Weighted Eciency
92.5% 92.5%
Total Harmonic Distortion
Max. Total Harmonic: <5%
Max. Single Voltage Harmonic: <2%
Max. Total Harmonic: <5%
Max. Single Voltage Harmonic: <2%
Max. Total Harmonic: <5%
Max. Single Voltage Harmonic: <2%
Max. Total Harmonic: <5%
Max. Single Voltage Harmonic: <2%
Output Voltage Regulation
±2% ±2% ±2% ±2%
Maximum Output Current
1ms Peak: 100AAC @ 240VAC, 200AAC @ 120VAC
100ms RMS: 70.7AAC @ 240VAC
1ms Peak: 50AAC @ 240VAC
100ms RMS: 35.35AAC @ 240VAC
1ms Peak: 100AAC
100ms RMS: 70.7AAC
1ms Peak: 50AAC
100ms RMS: 35.35 AAC
Overload Capacity
100ms Surge: 16.97kVA
5 seconds: 12kVA
30 minutes: 9kVA
100ms Surge: 8.5kVA
5 seconds: 6.0kVA
30 minutes: 4.5kVA
100ms Surge: 16.3kVA
5 seconds: 11.5kVA
30 minutes: 7.9kVA
100ms Surge: 8.2kVA
5 seconds: 5.8kVA
30 minutes: 4.0kVA
AC Input Voltage Range (Adjustable)
(L1 or L2) 70 to 280VAC (L1-N, L2-N) 85 to 140VAC 170 to 290VAC (L-N) 170 to 290VAC
AC Input Frequency Range (Default)
54 to 66Hz @ 60Hz (45 to 55Hz @ 50Hz) 54 to 66Hz @ 60Hz (45 to 55Hz @ 50Hz) 45 to 55Hz @ 50Hz (54 to 66Hz @ 60Hz) 45 to 55Hz @ 50Hz (54 to 66Hz @ 60Hz)
Grid-Interactive Voltage Range
(L1-N or L2-N) 106 to 132VAC (L1-N or L2-N) 108 to 132VAC, default 208 to 252VAC (EN50438) (L-N) 208 to 252VAC, default
Grid-Interactive Frequency Range
59.3 to 60.5Hz 59.3 to 60.5Hz, default 57.0 to 61.0Hz (EN50438) 57.0 to 61.0Hz, default
Maximum AC Input Current
50AAC 50AAC 50AAC 50AAC
Continuous Battery Charge Output
115.0ADC 57.5ADC 100.0ADC 50.0ADC
DC Input Voltage Range
40 to 64VDC 40 to 64VDC 40 to 64VDC 40 to 64VDC
Temperature Range
Rated: -20 to 50°C (power derated above 25°C)
Maximum:-40 to 60°C
Rated: -20 to 50°C (power derated above 25°C)
Maximum:-40 to 60°C
Rated: -20 to 50°C (power derated above 25°C)
Maximum:-40 to 60°C
Rated: -20 to 50°C (power derated above 25°C)
Maximum:-40 to 60°C
Accessory Ports
Remote Temperature Sensor, MATE3 & HUB Communications Remote Temperature Sensor, MATE3 & HUB Communications
Non-Volatile Memory
Yes Yes Yes Yes
Field Upgradable Firmware
Yes Yes Yes Yes
Chassis Type
Vented Vented Vented Vented
Certications
Listed to UL1741, CE, CSA C22.2 No. 107.1, IEC
62109-1, AS4777.2, AS4777.3, EN61000-6-1,
EN61000-6-3, EN61000-3-2, EN61000-3-3,
AS3100, RoHS compliant per directive 2011/65/EU
Listed to UL1741, CE, IEC-62109-1 ETL, CSA
C22.2 No. 107.1, RoHS compliant per directive
2011/65/EU, FCC Class B, EN61000-6-1,
EN61000-6-3, EN61000-3-2, EN61000-3-3
IEC 62477-1, AS4777.2, AS477.3,
EN61000-6-1, EN61000-6-3, EN61000-3-2,
EN61000-3-3, AS3100, CE, RoHS compliant per
directive 2011/65/EU
IEC 62109-1, IEC 62477-1, AS4777.2, AS477.3,
EN61000-6-1, EN61000-6-3, EN61000-3-2,
EN61000-3-3, AS3100, CE, ROHS compliant
per directive 2011/65/EU
Warranty
Standard 5 year Standard 5 year Standard 5 year Standard 5 year
Weight (lb/kg)
Unit: 125.0 / 56.7
Shipping: 140.0 / 63.5
Unit: 82.0 / 37.2
Shipping: 94.0 / 42.6
Unit: 125.0 / 56.7
Shipping: 140.0 / 63.5
Unit: 81.0 / 36.7
Shipping: 93.0 / 42.1
Dimensions H x W x D (in/cm)
Unit: 28 x 16 x 8.7 / 71 x 40.6 x 22.1
Shipping: 34.5 x 21 x 14.5 / 87.6 x 53.3 x 36.8
Unit: 28 x 16 x 8.7 / 71 x 40.6 x 22.1
Shipping: 34.5 x 21 x 14.5 / 87.6 x 53.3 x 36.8
Unit: 28 x 16 x 8.7 / 71 x 40.6 x 22.1
Shipping: 34.5 x 21 x 14.5 / 87.6 x 53.3 x 36.8
Unit: 28 x 16 x 8.7 / 71 x 40.6 x 22.1
Shipping: 34.5 x 21 x 14.5 / 87.6 x 53.3 x 36.8
Energy Storage Solutions
OutBack also provides a wide range of energy storage solutions for keeping systems UL1741 rated end-to-end.
EnergyCell GH (Front Terminal Battery) EnergyCell RE (Front Terminal Battery) EnergyCell RE (Top Terminal Battery) Integrated Battery Racks (2 & 3 Shelf Options)