- Outback Power Systems, Inc. Battery Charger User Manual

900-0111-01-00 Rev A 15
Installation
Location and Environmental Requirements
The International Series GFX inverters can be located outdoors, but OutBack still recommends that
they be protected from the environment.
If protected from the environment, the inverter can mount in any position or orientation. If exposed to the
environment, it cannot be placed upside-down to ensure that water will not accumulate under the DC
cover. (It can be mounted in any other position or orientation.)
For installations where the inverter may be exposed to water spray, the inverter must be mounted either
with the base down (shelf mounting) or with the AC wiring compartment facing down (wall mounting). If
mounted with the base down, water cannot be allowed to accumulate around the inverter’s base. There is a
drainage system on the base of the inverter to dispel condensation. If submerged, water can enter this drain
and cause failure.
The inverter will perform more efficiently in locations offering plenty of air circulation. The recommended
minimum clearance is 5 to 10 cm (2 to 4 inches) on all sides of the inverter.
The inverter will function to all of its specifications if operated in a range of 0 °C to 50 °C (32 °F to 122 °F).
Note that the inverter’s maximum wattage will derate in temperatures above 25 °C.
The inverter will function, but will not necessarily meet its specifications, if operated in a temperature range
of –40 °C to 60 °C (–40 °F to 140 °F). This is also the allowable temperature range for storage. (The
specifications are listed in the International Series GFX Operator’s Manual.)
Dimensions
Figure 4 Dimensions
Width
21 cm (8.25”)
Length 41 cm (16.25”)
Height
33 cm (13”)