Extra data identifier: ‘00’ to ‘99’, this is an ASCII expression of a 8 bit byte with bits 1 through 7 being
used.
Bit: 7 extra data numeric sign
0: positive value
1: negative value
Bits: 1-6
0: Accumulated AH shunt ‘A’
1: Accumulated kWH shunt ‘A’
2: Accumulated AH shunt ‘B’
3: Accumulated kWH shunt ‘B’
4: Accumulated AH shunt ‘C’
5: Accumulated kWH shunt ‘C’
6: Days since full
7: Today’s minimum SOC
8: Today’s net input AH
9: Today’s net output AH
10. Today’s net input kWH
11: Today’s net output KWH
12: *Charge factor corrected Net battery AH
13: *Charge factor corrected Net battery kWH
14-35 Reserved
kWH values: ‘00000’ to ‘65535’, 000.00 to 655.35 Kwatts
AH values: ‘00000’ to ‘65535’, 0 to 65535
Days since full output: ‘00000’ to ‘09999’, 0.0 to 999.9
Minimum SOC output: ‘00000’ to ‘00100’, 0 to 100 percent
*MATE version 4.04 and above
FLEXnet DC battery voltage: ‘000’ to ‘999’, A 24.8 Vdc battery voltage will be sent as ‘248’.
Battery State of charge: ‘000’ to ‘100’, 0 to 100 percent.