Mate Specifications

47
STATUS/FX/DISCON-----------P00
acin freq No
too high
DOWN STATUS PORT
STATUS/FX/DISCON-----------P00
acin voltage No
> max
DOWN UP TOP PORT
STATUS/FX/DISCON----------P00
acin freq No
too low
DOWN UP TOP PORT
STATUS/FX/DISCON-----------P00
acin voltage No
< min
DOWN UP TOP PORT
STATUS/FX/PAGE2----------------
choose category:
PG2 DISCON SELL MAIN
STATUS/FX/DISCON----------------
end of DISCON menu
UP TOP STATUS
FX DISCON(NECT) Screens
DISCON(NECT) Screens
• acin freq too high:screendisplays“Yes”iftheACsourceexceeds69Hz*andtheFXdisconnectsfromthe
source
• acin freq too low:displays“Yes”iftheFXdisconnectsfromanACsourcebelow51Hz**
• acin voltage > max:thesourceoftheACvoltageexceedstheFXmaximumof140VAC***(defaultvalue)
• acin voltage < min:thesourceoftheACvoltagefallsbelowtheFXminimumof108VAC****(default)
International FX *56 Hz **44 Hz ***270VAC ****207VAC
STATUS/FX/PAGE2-----------------
choose category:
PG2 DISCON SELL MAIN
STATUS/FX/PAGE3-----------------
choose category:
PG2 DISCON SELL MAIN
STATUS/FX/SELL-------------
stop sell 15
reason
STATUS PORT
PressSTATUStoreturntothe
MAINMenu.
PressMAINtoreturntothe
STATUSMenu
FX SELL Screen
• stop sell reason: displays a numerical value
(15insamplescreenshownhere)indicating
areasonagrid-tiedFXhasstoppedselling
power to the utility grid; this screen is used
for troubleshooting by OutBack Power System
technicians.
Stop SELL Reasons
0
1Frequencyshigreaterthanlimits
2 Island-detectedwobble
3 VACovervoltage
4 Phaselockerror
5 Chargediodebatteryvoltfault
6
7 Silentcommand
8 Savecommand
9 R60oatgofast
10 R60oatsilentrelay
11 Currentlimitsell
12 Currentlimitcharge
13
14 Backfeed
15 BrutesellchargeVACover