Owner's Manual Owner's manual
900-0137-01-00 Rev A 15
FLEXnet DC Data Stream
This is the data stream generated for a FLEXnet DC (FNDC) battery monitor connected to the system.
The data stream for is 52 characters long. An example is 0,4,0000,0126,0000,02,00023,287,099,001,00,33,062.
The items shown in Table 18 define the data stream by character.
Specific descriptions for each category begin on page 16.
Table 18 Data Stream Matrix for FLEXnet DC Battery Monitor
Character Definition Character Definition
1 New Line character, ASCII (10). Denotes the start of
the status page.
27 Hundreds digit of extra data identifier.
2 Tens digit of Port number. 28 Tens digit of extra data identifier.
3 Units digit of Port number. 29 Units digit of extra data identifier.
4 Comma, ASCII (44). Used as a data separator. 30 Comma, ASCII (44). Used as a data separator.
5 Device type 4, ASCII (52). Indicates battery monitor. 31 Tens digit of battery voltage.
6 Comma, ASCII (44). Used as a data separator. 32 Units digit of battery voltage.
7 Hundreds digit of Shunt A current. 33 Tenths digit of battery voltage.
8 Tens digit of Shunt A current. 34 Comma, ASCII (44). Used as a data separator.
9 Units digit of Shunt A current. 35 Hundreds digit of battery state of charge percentage.
10 Tenths digit of Shunt A current. 36 Tens digit of battery state of charge percentage.
11 Comma, ASCII (44). Used as a data separator. 37 Units digit of battery state of charge percentage.
12 Hundreds digit of Shunt B current. 38 Comma, ASCII (44). Used as a data separator.
13 Tens digit of Shunt B current. 39 Enable flag for Shunt A.
14 Units digit of Shunt B current. 40 Enable flag for Shunt B.
15 Tenths digit of Shunt B current. 41 Enable flag for Shunt C.
16 Comma, ASCII (44). Used as a data separator. 42 Comma, ASCII (44). Used as a data separator.
17 Hundreds digit of Shunt C current. 43 High digit of status flag.
18 Tens digit of Shunt C current. 44 Low digit of status flag.
19 Units digit of Shunt C current. 45 Comma, ASCII (44). Used as a data separator.
20 Tenths digit of Shunt C current. 46 Tens digit of battery temperature.
21 Comma, ASCII (44). Used as a data separator. 47 Units digit of battery temperature.
22 Tens digit of extra data identifier. 48 Comma, ASCII (44). Used as a data separator.
23 Units digit of extra data identifier. 49 Hundreds digit of Checksum.
24 Comma, ASCII (44). Used as a data separator. 50 Tens digit of Checksum.
25 Ten thousands digit of extra data identifier. 51 Units digit of Checksum.
26 Thousands digit of extra data identifier. 52 Carriage return, ASCII (13). Denotes the end of the
status page.
Start of Status Page
Port Address
separator
Device Type 4
separator
Shunt A Amps
separator
Shunt B Amps
separator
Shunt C Amps
separator
Extra Data Identifier
separator
Extra Data
separator
Battery Voltage
separtator
State of Charge
separator
Shunt 1 Enable
Shunt 2 Enable
Shunt 3 Enable
separator
Status Flags
separator
Battery
Temperature
separator
Checksum
End of status page
ASCII
code
10 X X 44 52 44 X X X X 44 X X X X 44 X X X X 44 X X 44 X X X X X 44 X X X 44 X X X 44 X X X 44 X X 44 X X 44 X X X 13
Char. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52