OutBack Power Programming Guide

900-0125-12-01 Rev A
©2017 OutBack Power Technologies. All Rights Reserved.
Page 30
Page 31
M-1. AGS continued
BATTERY STATUS
INVERTER
GEN
CHARGER
EVENTS
FAVORITE
AC INPUT
1.5
kW
0.1
kW
0.0
kW

G
G
OutBack Power
1.5 kW
1.5 kW
115 V
1.5 kW
85%
28.5 V
System
OK
0.00 kW
0.0 kW

G
G
 AGS Functional Test
Before any further programming, confirm that the generator is working properly. Using the generator’s own
controls, manually turn it on and then shut it off.
Next, test the remote start functionality. Go to the Generator Status screen using the GEN hot key.
To test the AGS function through the MATE3s:
1. Press the GEN hot key to bring up the Generator Status screen.
2. Press the <ON> soft key and wait for the generator to start running.
3. Press the <OFF> soft key to shut the generator off.
4. Press the <AUTO> soft key to put the generator in AUTO mode.
(Automatic functions need to be tested separately.)
5. Press the <BACK> soft key to return to the Home screen.
 AGS Troubleshooting
If the generator fails to start or connect, there are many possible reasons. The steps below provide
initial guidance for troubleshooting.
The AGS timers have not been activated by
the present conditions.
Check to make sure at least one AGS timer is active.
(See page 29.) If the timers are not active, check the
AGS settings. Compare all settings against the Start
and Stop Reasons table. (See page 31.)
AGS starts the generator
but AGS Fault appears
anyway.
Generator output does not meet inverter
requirements.
Check generator voltage and frequency.
To clear an AGS fault, go to the GEN hot key screen.
Press the <OFF> soft key.
A Stop condition is active. This could include
Quiet Time.
AGS does not send a start
command under expected
conditions.
AGS is not enabled.
Check Mode in the GEN hot key screen. Ensure
AGS Enabled is set to Y. (See page 25.)
Possible Cause
AGS sends a command
but the generator does
not start.
Open circuit between AUX connection and
generator.
Symptom Possible Remedy
Ensure the generator will start using its own controls.
Ensure it will start using the <ON> soft key in the
GEN hot key screen. Check all conductors, including
external relays, contactors, or other devices.
Compare all settings against the Start and Stop
Reasons table. (See page 31.)
Generator output is not reaching inverter input.
Check all circuit breakers and switches. Measure AC
voltage at inverter input terminals.
 Start and Stop Reasons
After AGS has started the generator, the GEN hot key screen shows
the reason for starting under Last Run. The first two columns in
the table below are a list of start reasons.
The remaining columns display the possible reasons for the generator to stop. The possible stop reasons
are connected to the start reasons. For example, a generator which started due to Load kW can stop due
to reduction of load kilowatts, due to Quiet Time, or manually. However, it will not stop due to battery
state of charge (SOC) or any of the other reasons.
NOTES
 "Setting" refers to the Interval Days setting in the State-of-Charge (SOC) Start screen as depicted on page 28.
 “CPM” (Charged Parameters Met) refers to the full-charge parameters of the FLEXnet DC (FN-DC) Battery Monitor as defined
on page 22. The FN-DC must be installed in the system.
 The conditions of the Inverter In Float or Silent column will stop the generator if the inverter reaches these charging
stages before the conditions of the other columns take effect.
 The conditions of the Stop SOC% column apply as long as Days Since Parms Met does not exceed Interval Days.
The generator will be shut off upon reaching the Stop SOC% setting as shown on page 28.
 The conditions of the Stop at 100% SOC column apply if Days Since Parms Met equals or exceeds Interval Days.
The generator will ignore the Stop SOC% setting and continue running until the battery SOC is at 100%. (This function does
not operate if Enable Full Charge is set at N, or if the Interval is set at 0.)
 The conditions of the FN-DC Charge Parms Met (CPM) column apply when Days Since Parms Met equals or exceeds
Interval Days and Enable Full Charge (100% SOC) is disabled as noted above. These conditions also apply if for any reason
the charge parameters are not met when the batteries reach 100% SOC as noted above. The generator will continue to run
until the FN-DC's charge parameters have been met.
24 Hour Batt V Yes Stop
Stop if days
since CPM
< setting
Stop if days
since CPM
> setting
2 Hour Batt V Yes Stop
Stop if days
since CPM
< setting
Stop if days
since CPM
> setting
2 Min Batt V Yes Stop Stop
Inverter
in Float
or Silent
START
REASONS
Global
Rebulk
Stop
SOC %
FN-DC
Charge
Parms Met
(CPM)
Below
Load
kW
Start SOC % Yes Stop
Stop if days
since CPM
< setting
Stop if days
since CPM
> setting
Load kW
Stop
Exercise
Must Run Start Yes
Manual Yes
If Auto
selected
If Auto
selected
Stop if days
since 100%
> setting
Stop if days
since 100%
> setting
Stop at
100%
SOC
Stop if days
since 100%
> setting
Stop
Stop
Quiet
Time
Stop
Stop
Stop
Stop
Exercise
Time
Expires
Stop
Stop
Stop
Stop
Manual
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
High
Batt
Voltage
Stop
Below
Load
kW
Stop
STOP REASONS
AGS (Testing)MATE3s Settings