Outback FXR Series Operator's Manual
Metering
46 900-0167-01-01 Rev A
Load
displays kilowatts and AC amperage consumed by devices on the inverter’s output. It can be
the same as
Invert
.
Buy
displays the kilowatts and AC amperage brought into the inverter’s input for both charging and
loads. This is usually a total of
Charge
and
Load
.
Battery
displays the uncompensated battery voltage.
AC Out
displays the AC voltage measured at the inverter’s output. If an AC source is present, this
reading is usually the same as
AC In
.
AC In
displays the AC voltage measured at the inverter’s input from an AC source. This number may
be erratic or inaccurate upon first connection until the inverter synchronizes with the input source.
AUX
displays the current status of the inverter’s Auxiliary (
A
UX
) 12-volt output. (See page 41.)
A diode symbol may appear to the left of the screen name to indicate “diode charging” mode. This is
a mode that allows fine control of charging, selling, and load support. It does not visibly affect
operation.
The
<
Graph
>
soft key brings up a series of screens which plot various types of data over time
on the system display screen.
Battery Screen
The
<Next>
soft key brings up a screen showing charger status, charger settings, and battery
voltage and temperature information.
Figure 11 Battery Screen
Screen items:
Actual
displays the uncompensated battery voltage.
Absorb
displays the charger’s Absorption voltage setting. (See page 31.)
Float
displays the charger’s Float voltage setting. (See page 32.)
Equalize
displays the charger’s Equalization voltage setting. (See page 36.)
Temp
Comp
displays the corrected battery voltage using temperature readings from the Remo
te
Tempe
rature Sensor (RTS). If no RTS is present,
Temp
Comp
and
Actual
will read the same. (See
page 3
6
.)
Batt
Temp
displays the battery temperature in degrees Celsius, as measured by the RTS. This
readi
ng is only valid for port 1 on the HUB product. If other ports are sele
cted, or if no RTS is
present, the characters ### will be displayed.
Re-Float
displays the Re-Float setting which was programmed into the inverter’s charger. This is the
voltage used
for the inverter to return from Silent mode to the float stage. (See page 32
.)
Sell RE
voltage is the target voltage used by the inverter for the grid-interactive and other
Offset
functions when the charger is otherwise inactive. (See pages 16 an
d 37.)
The
<
Warn
>
and
<
Error
>
key
s bring up screens with various fault information. See the next section.
NOTE
:
The charger settings cannot be adjusted on this screen.
A
n arrow will appear to the right of
Absorb
,
Float
, or
Equalize
to
indicate that the charger is in that stage. The arrow will not appear
if the charger is in the Bulk stage, or if it is inactive.