Specifications Sheet
2
OutBack reserves the right to make changes to the products and information contained in this document without notice.
Copyright © 2017 OutBack Power. All Rights Reserved. OutBack is a registered trademark of The Alpha Group.
EnergyCell NC Front Terminal/Top Terminal SPECIFICATIONS 05/2017
Models:
EnergyCell 106NC (Top Terminal) EnergyCell 200NC (Front Terminal)
Cells per Unit
6 6
Voltage per Unit
12VDC 12VDC
Operating Temperature Range
(w/ Temperature Compensation)
Discharge: -40 to 71°C (-40 to 160°F) Charge: -23 to 60°C (-10 to 140°F) Discharge: -40 to 71°C (-40 to 160°F) Charge: -23 to 60°C (-10 to 140°F)
Optimal Operating Temperature Range
23 to 27°C (74 to 80°F) 23 to 27°C (74 to 80°F)
Recommended Maximum
Charging Current Limit per String
30ADC 53ADC
Float Charging Voltage
13.62VDC unit average at 25°C (77°F) 13.62VDC / unit average at 25°C (77°F)
Equalization and
Cycle Service Charging Limits
14.4VDC unit average at 25°C (77°F) 14.4VDC / unit average at 25°C (77°F)
Self Discharge
Battery can be stored up to 6 months at 25°C (77°F) before a freshening charge is required.
Batteries stored at temperatures greater than 25°C (77°F) will require recharge sooner than batteries stored at lower temperatures.
Temperature Compensation
Factor (Charging)
5mV per °C per cell (2V) 5mV per °C per cell (2V)
Terminal
Threaded copper alloy insert terminal to accept ¼”-20 UNC bolt Threaded copper alloy insert terminal to accept ¼”-20 UNC bolt
Terminal Hardware Initial Torque
110in-lbs (12.4Nm) 110in-lbs (12.4Nm)
Weight (lb/kg)
69 / 31 131 / 60
Dimensions H x D x W (in/cm)
*
8.52 x 13.42 x 6.80 / 216.4 x 340.9 x 172.7 12.60 x 22.01 x 4.95 / 32.0 x 55.09 x 12.6
* Batteries to be installed with 0.5 in (12.7 mm) spacing minimum and free air ventilation.
Discharge in Hours:
12V Ampere Hour Capacity to 1.75 Volts Per Cell at 77°F (25°C)
1 2 3 4 5 8 12 20 24 48 100
EnergyCell 106NC
49.2 61.5 70 76 80.6 89 94.2 100 101 102.6 106
EnergyCell 200NC
103 120 132 139.6 145.5 158.4 168 178 181.4 189.6 200
Cycle Life Improvement—EnergyCell RE vs EnergyCell NC
Cycle Count
Depth of Discharge
* Assumes partial state of charge (PSoC) operation at 50-80%.
9,000
8,000
7,000
6,000
5,000
4,000
3,000
2,000
1,000
0
10% 20% 30% 50% 80% 100%
EnergyCell RE
EnergyCell NC
*
Battery Characteristics—Capacity vs Temperature
% of Capacity
Temperature
105
100
95
90
85
80
75
70
65
60
55
50
-30°C -20°C -10°C 0°C 10°C 20°C 30°C 40°C
C/100
C/20
1
Consult local and regional electrical code for proper installation of energy storage requirements.