Outback EnergyCell RE High Capacity Manual

PowerSafe DDm
Publication No. US-DDm-IM-003 Page 5
November 2003 www.enersysinc.com
SYSTEM LAYOUT
Before installing the battery system, lay out
available floor space including aisles for
installation, maintenance and possible cell
replacement. Consult the local installation
considerations as determined in Section 5 of
the Safety, Storage, Operating and
Maintenance Manual for the VRLA Modular
Battery Systems. Recommended clearance
between these racks and any objects (including
walls and equipment) is 4 inches (102 mm).
1. Layout the system position for either a
SINGLE-STACK (Figure 4), a MULTI-
STACK (Figure 5), or MULTI-STACK WITH
ZERO SEPARATION (Figures 6, 7 & 8)
configuration with the dimensions defined in
Table 2.
2. Locate the position of the floor anchors
using the frame base beams.
3. Mark floor with the position of the floor
anchors.
“L”
FRONT
L
L
FRONT
D
D = DISTANCE BETWEEN BASES (VARIABLE)
MULTI-STACK
FIGURE 5
M
M
FRONT
DDm50 MULTI-STACK
WITH ZERO SEPARATION
FIGURE 6
W=
DDm85 = 17.46
DDm100 = 20.47
FRONT
M
M
W
7.67
DDm85/100 MULTI-STACK
WITH ZERO SEPARATION
FIGURE 7
FRONT
M
M
19.81
Dm125 MULTI-STACK
WITH ZERO SEPARATION
FIGURE 8
NOTE:
Floor anchoring is REQUIRED for all
installations.
Allow sufficient clearance between
adjacent walls or equipment for
proper installation of anchors. Please
check your local codes for clearances
required.
Floor anchor design (including, but
not limited to size, quantity, and
capacity) and installation are the
responsibility of the user/installer.
Follow the user’s design and the
manufacturer’s instructions.
10.75
SINGLE-STACK
FIGURE 4