FlexMax FM100 AFCI Installation

900-0253-01-00 Rev A
29
Status and Information
LED Indicators
The FLEXmax 100 charge controller has no graphical display. It is equipped with four LED indicators.
IMPORTANT:
The LED indicators do not necessarily tell the amount the controller is actively charging.
The
C
HARGING
indicator may still indicate Absorption and the
S
TATUS
indicator may indicate
rising battery voltage, even if another charging source is doing most of the work.
NOTE:
The LED indicators are intended as pointers rather than exact messages. See the next page
for a more specific description of each indicator. Consult the system display for more
information on controller status (see page 35).
Table 2 LED Indicators
Indicators
CHARGING
STATUS
AUXILIARY
FAULT
A
ll flash twice, then turn off (with PV power available) = Rapid Shutdown
Controller Status
Off = less than 10 W PV available
Bulk, Equalize, or GT Mode
A
bsorption
Float
Bulk or Absorption
Float
GT Mode
Battery Discharge
Critical Battery Discharge
Equalize
AUX Active
Ground Fault Shutdown or other fault
A
rc Fault Shutdown
Voltage
Battery rest
Float
≥ 1.91 Vpc
<1.91 Vpc
< 1.75 Vpc
≤ EQ
AUX Active
Pattern